7.7.7 Internal process setpoint setting

If necessary, the process controller can also be operated without external
process setpoint. An internal process setpoint may be set with this parame-
ter.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
INTERNAL SET POINT

:EDIT
Default value:
Setting range:
Information
The actuator only reacts to the preset internal setpoint if the
parameter is set to
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT

:EDIT
Default value:
È
Description of the parameter settings:
PID-INTERN
Process control via internal process setpoint
PID-EXTERN
Process control via external process setpoint
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
PROCESS CONTROL PID (M1I)
INTERNAL SET POINT (M1I14)
M1I14
0 %
¿:OK C:ESC
0 %
0
to
100 %
PID-INTERN
PROCESS CONTROL PID (M1I)
PID TYPE (M1I1C)
M1I1C
PID TYPE
PID-EXTERN
¿:OK C:ESC
PID-EXTERN
.
Actuator controls
PID TYPE
65