Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
6.2

Operation mode LOCAL

6.2.1 Push-to-run operation or self-retaining: set for operation mode LOCAL

36
Ò Set selector switch to position Local control (LOCAL).
Display indicates:
 ‚ LOCAL MODE
.
The actuator can be controlled via OPEN - STOP - CLOSE push buttons
.
of the local controls.
Faults and warnings without automatic reset can be confirmed with the
Reset push button.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
EDIT
MAINTAINED LOCAL
OPEN + CLOSE (STOP)

↵:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
OFF
Push-to-run operation on, self-retaining off:
Actuator runs in direction OPEN or CLOSE, depending on the operation
command issued. If the operation command is removed, the actuator stops.
OPEN
In direction OPEN = self-retaining (direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuators continues
even if the operation command is removed (self-retaining). The actuator is
stopped via the STOP command or once the end position OPEN is reached.
CLOSE
In direction CLOSE = self-retaining (direction OPEN push-to-run operation):
After an operation command in direction CLOSE, the actuators continues even
if the operation command is removed (self-retaining). The actuator is stopped
via the STOP command or once the end position CLOSED is reached.
OPEN + CLOSE (STOP)
In direction OPEN and CLOSE = self-retaining:
After an operation command the actuator continues in direction OPEN or
CLOSE, even if the operation command is removed (self-retaining). The
actuator is stopped via the STOP command in an the end position.
OPEN+CLOSE (NO STOP)
In direction OPEN and CLOSE = self-retaining without STOP
A direct reversal of the direction of without STOP command is possible.
0
S0
MAINTAINED LOCAL (M1310)
M1310
OPEN + CLOSE (STOP)
Manual