Setting The Profibus Dp Address Via Local Controls - AUMA AUMATIC AC 01.1 Short Instructions

Actuator controls, profibus dp
Hide thumbs Also See for AUMATIC AC 01.1:
Table of Contents

Advertisement

Actuator controls AUMATIC AC 01.1 / ACExC 01.1
Profibus DP
3.6

Setting the Profibus DP address via local controls

10
This clause only describes the setting of the actuator address (slave
address). For further detailed instructions on the indication, operation and
setting of the AUMATIC refer to the operation instructions of the actuator
(multi-turn actuator SA(R) ... / part-turn actuator SG ...
with AUMATIC AC ...).
Factory setting:
.
Slave address: 2
.
.
Set selector switch at the AUMATIC to position OFF (0), figure F-1.
.
Switch on supply voltage.
Select menu indication M0:
Press push-button
(S0, S1, S2, S3 or S4) longer than 2 seconds:
Figure
F-1
.
Select
SETTINGS
Figure
F-2
.
Confirm the selection
Figure
F-3
.
Select
PROFIBUS DP1
Figure
F-4
.
Confirm the selection
Figure
F-5
.
Select
with push-button
EDIT
Figure
F-6
Confirm the selection
in one of the status indications
C
> 2 Sec.
with push-button
:
MAIN MENU
M1
LANGUAGE / CONTRAST
SETTINGS
OPERATIONAL DATA
SETTINGS
with
SETTINGS
M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
by pushing
several times:
SETTINGS
M1B
POSITIONER
SPEED SETTING
PROFIBUS DP1
with
PROFIBUS DP1
PROFIBUS DP1
M1B0
VIEW
EDIT
:
PROFIBUS Dp1
M1B1
VIEW
EDIT
with
:
EDIT
Short instructions
MAIN MENU
LANGUAGE /CONTRAST
SETTINGS
OPERATIONAL DATA
:
.
M0

Advertisement