Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP

6.5.2 Source for initiation (failure source): set for failure operation

6.5.3 Actuator reaction (failure position): set on loss of signal

42
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
EDIT
FAILURE SOURCE
E1 OR E2 FEEDBACK

¿:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
SETPOINT E1
Failure behaviour is initiated if setpoint E1 or actual value E2 fail or in case
of loss of the bus communication.
The monitoring depends on the preset setpoint range, e.g.:
E1 = 4 – 20 mA, E1 lower than 3.7 mA = loss of signal
E1 = 10 – 20 mA, E1 lower than 9.7 mA = loss of signal
Monitoring of E1 = 0 – 20 mA is not possible
E1 OR E2 FEEDBACK
.
Failure behaviour is initiated if setpoint E1 or feedback E2 fail.
.
The following is monitored:
for actuators with potentiometer: Cable break is detected
.
for electronic position transmitter RWG 4 – 20 mA in actuator:
E2 lower than 3.7 mA = signal loss
for MWG in actuator:
Communication faults and MWG internal faults are recognised
E1, E2 OR E4 FEEDBACK
Failure behaviour is initiated if setpoint E1, feedback E2, or actual process
variable E4 fail
BUS INTERFACE
A failure behaviour is initiated in case of loss of bus communication
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
EDIT
FAILURE POSITION
FAIL AS IS

¿:OK C:ESC
:EDIT
Default value:
Description of the parameter settings:
FAIL AS IS
The actuator stops in the current position.
FAILURE SOURCE (M1514)
M1514
E1 OR E2 FEEDBACK
FAILURE POSITION (M1512)
M1512
FAIL AS IS
Manual