Signals; Signals Via Fieldbus; Status Signals Via Output Contacts (Digital Outputs); Assignment Of Outputs - AUMA SG 12.1 Operation Instructions Manual

Control unit: electronic (mwg) with actuator controls aumatic ac 01.2 non-intrusive
Table of Contents

Advertisement

Signals

8.
Signals
8.1

Signals via fieldbus

Information
8.2

Status signals via output contacts (digital outputs)

Characteristics
8.2.1

Assignment of outputs

8.2.2

Encoding of outputs

8.3

Analogue signals

40
SG 05.1
SG 12.1/SGR 05.1
Feedback signals via fieldbus can be configured. Configuration is possible for both
data structure and data contents.
Configuration is defined via the GSD file only.
If required, download the GSD file (General Station Description) from the Internet:
www.auma.com
For information on the feedback signals via fieldbus and the configuration of the
parameters via fieldbus interface, refer to Manual (Device integration fieldbus) Profibus
DP.
(Option)
Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
The output signals DOUT 1
High active = output contact closed = signal active
Low active = output contact open = signal active
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values for DOUT 1 – 6: High active
(Option)
SGR 12.1 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profibus DP
6) can be assigned to various signals.
6 can be set either to high active or low active.