Operation mode FAILURE

6.5.1 Failure behaviour: switch on or off

The operation mode FAILURE enables an initiation of failure operations in
case of signal loss or loss of bus communication.
If the FAILURE mode is enabled, the display indicates:
 ‚ FAILURE MODE
Table of contents:
6.5.1 Failure behaviour: switch on or off
6.5.2 Source for initiation (failure source): set for the failure operation.
6.5.3 Actuator reaction (failure position): set on loss of signal
6.5.4 Preset position definition
6.5.5 Failure delay time setting
6.5.6 Failure behaviour for bus communication loss
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
FAILURE BEHAVIOUR

:EDIT
Default value:
Description of the parameter settings:
OFF
Failure behaviour is switched off.
GOOD SIGNAL FIRST
A failure operation is only initiated if no cable break is recognised after
switching on, but loss of signal is recognised later through cable break.
With this setting, it is ensured that the actuator does not perform a preset
failure action (failure position) when switched on without signal E1 con-
nected.
FAIL IMMEDIATE
A failure operation is initiated in case of cable break.
Information
If
FAIL IMMEDIATE
ately after the actuator is switched on if a cable break has occurred.
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
S0
FAILURE BEHAVIOUR (M15)
FAILURE BEHAVIOUR (M1510)
M1510
OFF
¿:OK C:ESC
OFF
is switched on, a failure operation is initiated immedi-