Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
7.14
External inputs for bus (option)
7.14.1 Signals assignation for operation commands
80
Parallel control via external inputs is possible for an AUMATIC with fieldbus
interface.
Four binary 24 V DC inputs and two analogue 0/4 – 20 mA inputs are avail-
able.
Irrespective of the signal assignment of these inputs, the fieldbus communi-
cation with the DCS will remain intact.
This value is set in the factory.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
EDIT
EXTERNAL INPUTS BUS
STANDARD
¿:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
STANDARD
Figure 15:
The external input signals are transferred to the process control system via
the fieldbus They do not influence the operation behaviour of the actuator.
Figure 15
1
External inputs
EXTERNAL INPUTS BUS (M410G)
M410G
STANDARD
2
Fieldbus interface
Manual