7.14

External inputs for bus (option)

7.14.1 Signals assignation for operation commands

80
Parallel control via external inputs is possible for an AUMATIC with fieldbus
interface.
Four binary 24 V DC inputs and two analogue 0/4 – 20 mA inputs are avail-
able.
Irrespective of the signal assignment of these inputs, the fieldbus communi-
cation with the DCS will remain intact.
This value is set in the factory.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
EDIT
EXTERNAL INPUTS BUS
STANDARD

¿:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
STANDARD
Figure 15:
The external input signals are transferred to the process control system via
the fieldbus They do not influence the operation behaviour of the actuator.
Figure 15
1
External inputs
EXTERNAL INPUTS BUS (M410G)
M410G
STANDARD