AUMATIC AC 01.1/ACExC 01.1 Profibus DP

7.16.4 Operating time monitoring

88
This function allows the monitoring of the operating time of the actuator. If
the actuator needs longer than the set time (
to move from end position OPEN to end position CLOSED, the following
.
warning signals are given (the actuator is not stopped):
.
.
Status indication
Status indication
Status indication
The warning signals are automatically cleared when a new operation com-
mand is executed.
When the actuator moves from an intermediate position to an end position,
the set monitoring time for the whole stroke is assigned in relation to the
remaining stroke/travel.
Switching the operating time monitoring on/off
Information
This parameter is also used to switch the monitoring of the max. number of
starts per hour and the max. running time per hour (page 84) on/off.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
EDIT
MONITOR TRIGGERS
FUNCTION ACTIVE

:EDIT
Default value:
È
Description of the parameter settings:
FUNCTION NOT ACTIVE
The operating time monitoring is switched off
FUNCTION ACTIVE
The operating time monitoring is switched on
Setting the max. permissible operating time
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
MAX. RUN TIME

:EDIT
Default value:
Setting range:
: operation mode OFF/LOCAL =
S0
S0/S6
: operation mode REMOTE =
S2
:
WARNING OPER. TIME
SPECIAL FUNCTIONS (M40)
MONITOR TRIGGERS (M4016)
M4016
¿:OK C:ESC
FUNCTION ACTIVE
MONITOR TRIGGERS (M18)
MAX. RUN TIME (M1812)
M1812
900 s
¿:OK C:ESC
s
900
4
to
36,000
seconds (4 seconds to 10 hours)
MAX. RUN TIME
parameter)
WRN + NR
WARNING