Actuator controls AUMATIC AC 01.1/ACExC 01.1 Control: Parallel Profibus DP Profibus DP with FO Modbus Modbus with FO DeviceNet à Foundation Fieldbus Manual Operation and setting...
Reference documents: Operation instructions (assembly, operation, commissioning) for actuator Manual (Fieldbus device integration) AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses from page 94). Table of contents Page Safety instructions ........5...
Page 3
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Page Operation mode ........31...
Page 4
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Page 7.10 Foundation Fieldbus interface 7.11 External inputs for bus (option) 7.11.1 Signals assignation for operation commands 7.12 Combination fieldbus/standard interface (option) 7.13 Monitoring and failure functions 7.13.1 Torque monitoring 7.13.2 Motor protection (thermal monitoring) 7.13.3...
Safety instructions General notes on safety Standards/directives AUMA products are designed and manufactured in compliance with recog- nised standards and directives. This is certified in a declaration of incorpora- tion and a declaration of conformity. The end user or the contractor of the plant must observe national laws and regulations regarding assembly, electrical connection, and commissioning on site.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Range of application AUMA actuator controls are exclusively designed for the operation of AUMA actuators. Other applications require explicit (written) confirmation by the manufac- turer. The following applications are not permitted, e.g.:...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Identification Name plate Each device is equipped with a name plate (figure 1). Figure 1 Name plate controls Identification data on the controls’ name plate: Figure 2 AC 01.1 P:1,5kW Com No: 1309595...
(push buttons and display) and perform settings (contents of these instructions). read in or out data or modify and save settings via the AUMA COM-AC programming software (option), using a computer (laptop or PC).
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Operation Local operation The local operation of the actuator is performed using the push buttons (figure 3). Figure 3 Push button OPEN Push button Reset Push button STOP Selector switch Push button CLOSE Indication lights/LEDs Ò...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Menu navigation via push buttons (for settings and indications) The push buttons of the local controls (figure 4) are used to view, edit, and show various indications on the display. Figure 4...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 3.3.2 Structural design and navigation The indications on the display are divided into 3 groups: Group = status indications Group = menu (settings) Group = diagnostic indications The active group is displayed on the top right corner of the display.
Operation and setting via AUMA COM-AC programming software Data from the actuator can easily be imported, exported and settings changed and saved using the AUMA COM-AC programming software (option) in combination with a computer. Depending on the version, the connection between computer and AUMATIC can be performed with cable (infra-red interface) or without cable (Bluetooth interface) (not included in these instructions) .
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Password change The following default password is set in the factory: 0000. Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) CHANGE PASSWORD (M1D) ò Step by step: 1. Set selector switch to position 0 (OFF).
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Language change in the display Æ Via the menu to parameter: MAIN MENU (M0) LANGUAGE/CONTRAS (M00) LANGUAGE (M010) EDIT M010 GERMAN ENGLISH ↵:OK C:ESC :EDIT Default value: GERMAN Setting range:...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Indications Status indications in the display The status indications on the display locally indicate the current operation states in plain text or as bar chart. Table of contents: 4.1.1 Status indication S0/S6 - operation 4.1.2 Status indication S4 - torque...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual RUNNING CLOSE Actuator runs logically CLOSE (remains set during operation pauses). OPEN POSITION End position OPEN reached. CLOSED POSITION End position CLOSED reached. SETPOINT POSITION Setpoint (modulating actuators only). È Description of the fault signals: See page 74.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Electronic name plate The electronic name plate provides information about the order data (impor- tant for enquiries in the factory) Table of contents: 4.3.1 Display indication: enable view 4.3.2 Electronic name plate: view 4.3.1 Display indication: enable view...
Page 18
CUSTOMER FIELD 1 adjustable (fields for customer input) CUSTOMER FIELD 2 adjustable (fields for customer input) Service information such as the AUMA service phone number and the AUMA Internet address can be indicated here: Table 4 Service data (M33) SERVICE PHONE...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Indication lights/LEDs The indication lights/LEDs locally display the different operation states as optical signal. The assignment of signals is freely selectable. Table of contents: 4.4.1 Standard indication 4.4.2 Configuration of the signals: view/edit 4.4.3 Blinking behaviour of indication lights/LEDs: view/edit...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 4.4.2 Configuration of the signals: view/edit Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) LOCAL CONTROLS (M13) LED 1 (LEFT HAND) (M1312) LED 2 (M1313) LED 3 (M1314)
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 4.4.3 Blinking behaviour of indication lights/LEDs: view/edit Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) LOCAL CONTROLS (M13) BLINKER (M1311) EDIT M1311 BLINKER OFF IN MIDPOSITION ↵:OK C:ESC ...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Signals Signals via fieldbus Feedback signals via Foundation Fieldbus can be configured. The configuration is only defined via the transducer blocks and/or the func- tion blocks. Information The DD (Device Description) can be downloaded from the Internet: www.auma.com...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Feedback via output contacts (binary) - (option) These feedback signals are only available if a parallel interface is available in addition to the fieldbus interface (refer to page 66). The output contacts can be used to indicate operation modes of the actuator or the controls as binary signals.
Page 24
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Signal Description Actuator is running from LOCAL, REMOTE, or in manual operation (without position transmit- ACTUATOR MOVING ter, only LOCAL or REMOTE operation are indicated). LSC (WSR) Limit switch CLOSE operated...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 5.2.2 Configuration alarm contacts (collective fault signal): view/edit Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) I/O 1 (M14) ALARM CONTACT (M1411) EDIT M1411 ALARM CONTACT FAULT GROUP 3 ...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 5.2.3 Output contacts 1 to 5: use as running indication (blinker) Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) I/O 1 (M14) OUTPUT CONTACT 1 (M1412) OUTPUT CONTACT 2 (M1413)
The valve position can be transmitted as a continuous signal by various position transmitters: The type of position transmitter/actual position source (E2) installed in the actuator is indicated here. This value is set in the factory and can only be changed by the AUMA ser- vice. Æ...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 5.3.2 Source of the torque signal E6: view This value is set in the factory and can only be changed by the AUMA ser- vice. Æ Via the menu to parameter:...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus For torque seating, the end positions OPEN and CLOSED of the limit switching should be set as close as possible to the end positions of the valve to minimise the deviation of the feedback.
5.3.5 Feedback signals (configuration) via analogue output 2: view Configuration of analogue output 2 (of the I/O). Designation in the wiring diagram: ANOUT2. This value is set in the factory and can only be changed by the AUMA service. Æ...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Operation mode Different operation modes (operation types) are available: The current operation mode is indicated in the first line of the display: LOCAL MODE OPEN 100 % RUNNING OPEN...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Operation mode LOCAL Ò Set selector switch to position Local control (LOCAL). Display indicates: LOCAL MODE The actuator can be controlled via OPEN - STOP - CLOSE push buttons of the local controls.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Operation mode REMOTE Ò Set selector switch to position Remote control (REMOTE). Display indicates: REMOTE MODE The actuator is controlled by external REMOTE commands OPEN - STOP - CLOSE.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Actuator only runs in direction OPEN or CLOSE while an operation com- mand is issued. If the operation command is removed, the actuator stops. OPEN+CLOSE (NO STOP) Self-retaining without STOP: A direct reversal of the direction of rotation without STOP command is pos- sible.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 6.4.2 EMERGENCY operation: switch on or off/signal behaviour definition Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) EMERGENCY BEHAVIOUR (M16) EMERGENCY BEHAVIOUR (M1610) EDIT M1610 EMERGENCY BEHAVIOUR ...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 6.4.4 EMERGENCY position definition If the EMERGENCY operation action FAIL TO PRESET EMERGENCY POSITION parameter) is set, the actuator runs to the EMERGENCY position stated here. Æ Via the menu to parameter:...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Fault State behaviour in case of bus communication loss The fault state behaviour of the Foundation Fieldbus function blocks (AOFB or DOFB) have to be configured to activate the failure behaviour in case of Foundation Fieldbus communication loss.
Page 38
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Information If FAIL IMMEDIATE is switched on, a failure operation is initiated immedi- ately after the actuator is switched on if a loss of signal has occurred. Source for initiation (failure source): set for failure operation Æ...
Page 39
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus FAIL OPEN The actuator runs to end position OPEN FAIL TO PRESET The actuator runs to a predetermined position. Preset position definition If the FAIL TO PRESET failure action ( FAILURE POSITION parameter) is set, the actuator runs to the preset position stated here.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Functions Type of seating: check/edit end positions Valve damage due to incorrect setting! NOTICE Ò The torque must suit the valve. Ò Only change the setting with the consent of the valve manufacturer.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Torque switching: check/set This setting is only possible for the non-intrusive version. For further information refer to page 8. Valve damage due to incorrect setting! NOTICE Ò The torque must suit the valve.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Limit switching setting This setting is only possible for the non-intrusive version For further information refer to page 8. Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) SET LIMIT SWITCHES (M10)
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Intermediate positions (option) The AUMATIC allows to define up to 8 intermediate positions. Condition The actuator is either equipped with: an MWG (for Non-Intrusive version), or a potentiometer (5 kΩ) or...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.4.2 Intermediate positions: switch on or off Each intermediate position ( ) may individually be switched POS.1 POS8. on/off. Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) INTERMED. POSITION (M1C) POS.1...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.4.4 Operation behaviour = actuator behaviour definition The reaction of the actuator upon reaching an intermediate position can be programmed via the parameters “ POS. 1: BEHAVIOUR POS. 8: BEHAVIOUR. Æ...
Page 46
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual È Description of the parameter settings: NOT USED No signal. POS¯¯¯¯¯O Signal active from reaching the intermediate position to end position OPEN. C¯¯¯¯¯POS Signal active from end position CLOSED to reaching the intermediate posi- tion.
Multiport valve function on = direct selection of intermediate positions possi- ble from both REMOTE and LOCAL. Information The function is either activated or deactivated via the EDIT menu. This value is set in the factory and can only be changed by the AUMA service.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.5.2 Check: Positioner active? The positioner must be available. This value is set in the factory. Æ Via the menu to parameter: MAIN MENU (M0) CONFIGURATION (M4) SPECIAL FUNCTIONS (M40) POSITIONER (M4000)
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.5.6 Operation behaviour = actuator behaviour definition The operation behaviour setting of the multiport valve intermediate positions is performed as described on page 45. 7.5.7 Intermediate positions signalling The signalling of the multiport valve intermediate positions is performed as described on page 45.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Positioner (operation mode SETPOINT MODE) The positioner records position setpoint E1 and position feedback E2 for comparison. Depending on the detected deviation, the actuator motor then runs in direction OPEN or CLOSE.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Figure 9 shows the modulating behaviour: Figure 9 E1 Nominal value T1 Outer dead band E2 Actual value T2 Max. error variable P1 Switch-on point T3 Inner dead band P2 Switch-off point in direction OPEN...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.6.3 Max. error variable (outer dead band): set manually The outer deadband determines the switching-on point of the actuator. The motor starts if the actual value (input signal E2) or a change in nominal value is higher than the max.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.6.5 Closing fully/opening fully (end position tolerance for setpoint E1) If the end positions cannot be reached due to inaccurate analogue setpoint signals (0/4 mA or 20 mA), a tolerance for the nominal value within the end position range can be set.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.6.7 Source of setpoint E1: view This value is set in the factory and can only be changed by the AUMA ser- vice. Æ Via the menu to parameter: MAIN MENU (M0)
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.6.8 Input range of setpoint 1: view/edit The parameters of this setting depend on the pre-set setpoint source SETPOINT E1 (M4100) parameter, page 54). Initial and end value via the Foundation Fieldbus interface In Foundation Fieldbus standard version, the setpoint E1 is transmitted via the AO function block.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Stepping mode (option) In stepping mode the operating time can be increased for the entire or any portion of the valve travel (refer to figure 10). Figure 10 Stepping range OPEN...
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus VIEW ENABLED The parameters for the stepping mode are indicated in the display. 7.7.2 Stepping mode: switch on or off Stepping mode can be individually activated for the directions OPEN and CLOSE.
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.7.4 ON and OFF times setting The ON or OFF times can be set individually for the directions OPEN and CLOSE. Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1)
The selector switch functions on the local controls (LOCAL, OFF, and REMOTE) may be either enabled or disabled. 7.8.1 Selector switch functions: enable/disable This value is set in the factory and can only be changed by the AUMA service. Æ Via the menu to parameter:...
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual EMERGENCY STOP function (option) As an option, the AUMATIC can be equipped with an EMERGENCY STOP push button. When engaged, this EMERGENCY STOP interrupts the 24 V AC control voltage of the contactors.
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.9.2 Feedback signals on the display The following indications are displayed in status indications Ü É EMERGENCY STOP NOT READY IND. EMCY STOP ACTIVE È Description of the displays:...
Page 62
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.10 Foundation Fieldbus interface All Foundation Fieldbus interface settings (including the device address assignment) are made via the Foundation Fieldbus. For this reason, the local operation (via the display) of the AUMATIC does not supply any Foundation Fieldbus relevant parameter.
Page 63
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.11 External inputs for bus (option) Parallel control via external inputs is possible for an AUMATIC with fieldbus interface. Four binary 24 V DC inputs and two analogue 0/4 – 20 mA inputs are avail- able.
Page 64
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual OPEN CLOSE CONTROL Figure 13: Conventional control of the actuator is possible either in OPEN - CLOSE duty or in modulating duty (setpoint of 0/4 – 20 mA). Selection between open - close and modulating duty is made via the MODE input (refer to page 53).
Page 65
In the event of loss of bus communication, the external inputs do not auto- matically take over! Information Please refer to the AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus manual (Device integration Fieldbus) for details on feedback signals. Switching between operation commands via fieldbus and external inputs Ò...
Page 66
BUS/REMOTE input. Information In the event of loss of bus communication, the external inputs do not auto- matically take over! Information Please refer to the AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus manual (fieldbus device integration) for details on feedback signals.
Page 67
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.13 Monitoring and failure functions Table of contents: 7.13.1 Torque monitoring 7.13.2 Motor protection (thermal monitoring) 7.13.3 Monitoring of the max. number of starts and the max. running time 7.13.4 Operating time monitoring 7.13.5 Reaction monitoring...
Page 68
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Setting range: ( = 0.0 to 5.0 seconds) 7.13.2 Motor protection (thermal monitoring) In order to protect against overheating and impermissibly high temperatures at the actuator, PTC thermistors or thermoswitches are embedded in the motor winding.
Page 69
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus THERMISTOR (AUTO) Automatic reset after the motor has cooled down. Not possible for explosion-proof version ACExC 01.1 7.13.3 Monitoring of the max. number of starts per hour and max. running time per hour...
Page 70
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Setting the max. permissible number of starts Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) MONITOR TRIGGERS (M18) MAX STARTS/HOUR (M1810) EDIT M1810 MAX STARTS/HOUR 1200 ↵:OK C:ESC ...
Page 71
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.13.4 Operating time monitoring This function allows the monitoring of the operating time of the actuator. If the actuator needs longer than the set time ( MAX. RUN TIME parameter) to move from end position OPEN to end position CLOSED, the following...
Page 72
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 7.13.5 Reaction monitoring The AUMATIC controls monitor the actuator reaction via the control unit of the actuator. If no reaction is recorded at the output drive of the actuator within a set time...
Page 73
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 7.13.6 Phase failure monitoring When connected to a 3-phase AC power supply, the electronics is supplied via two of the three phases. In case of losing one of the two phases, the controls are inoperable and the actuator stops.
Page 74
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Corrective action Fault indications and warning indications Faults interrupt or prevent electrical actuator operation. Warnings have no influence on the electrical actuator operation. They only serve information purposes. Fault and warning indications are shown on the display.
Page 75
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus 8.1.2 Status indication S1 - faults Faults are indicated within this group: FAULT IND. NO FAULT È Description of the fault indications: NO FAULT No fault has occurred. INTERNAL FAULT Internal fault has occurred.
Page 76
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual 8.1.3 Status indication S2 - warnings Warnings are indicated within this group: WARNING IND. NO WARNING È Description of the warnings: NO WARNING No warnings have occurred. WARNING RUN.TIME The preset running time for a travel between end position OPEN and end position CLOSED has been exceeded.
Page 77
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Ò Check wiring. P-FEEDBACK E4 LOSS Signal loss of process feedback E4 (only if process controller of logic sub-assembly is available and active). Ò Check wiring. FIBRE OPTIC LOSS Signal loss of fibre optic cable (only for bus with fibre optic loop topology).
Page 78
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Diagnostics Table of contents: 8.2.1 Operating data logging 8.2.2 Diagnostic indication (D) via the display 8.2.1 Operating data logging The operating data provides details e.g. about the running time, the number of starts, number of torque faults etc.
Page 79
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Table 10 Operational data TOTAL MOTOR RUNTIME Motor running time in the complete lifetime MOTOR RUNTIME Reset to 0 possible Number of start (motor starts) in the complete TOTAL STARTS lifetime...
Page 80
Manual 8.2.2 Diagnostic indications (D) via the display The information contained in the diagnostic indications is only provided for the AUMA service and for enquiries in the factory. 1. Change from the status indications (group ) to the diagnostic indica-...
Page 81
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Internal faults (D2) INTERNAL FAULT NO INTERNAL FAULT È Description of the displays: NO INTERNAL FAULT No internal fault has occurred THERMISTOR A fault in the TMS tripping device was detected during start-up. Remedy:...
Page 82
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Internal warnings (D3) INTERNAL WARNING NO INTERNAL WARNING È Description of the displays: NO INTERNAL WARNING No internal warnings have occurred NO FACTORY PARAMS No valid factory settings are available.
Page 83
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Software version of the logic (D6) LOGIC SFTWR. VER D6 È Description of the display: LOGIC SFTWR. VER Display of software version of the logic Potentiometer value (D7) ...
Page 84
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual MWG value (D9) MWG VALUE È Description of the display: MWG VALUE The current values are displayed here if an MWG is installed: in line 2 the value in end position CLOSED,...
Page 85
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus NOT CALIBRATED Remedy: Re-calibrate MWG (can only be performed in the factory). NO POSITION REFEREN. Remedy: Re-calibrate MWG (can only be performed in the factory). TORQUE SYSTEM FAULT Remedy: Exchange MWG.
Page 86
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual FF CAN No communication to the Foundation Fieldbus interface available. Remedy: must agree with the wiring diagram. Check wir- I/O STACK 1 (M4106) ing. Check I/O interface. Bluetooth hardware version (D14) ...
Page 87
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus FF hardware version (De) FF HRDWR.VER. È Description of the display: FF HRDWR.VER. Hardware version of the Foundation Fieldbus interface FF software version (Df) FF SFTWR.VER. È...
Page 88
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual FF node address (Di) FF-NODEADDRESS NODEADDRESS: 18/0X12 Stationmode: BASIC MACROCYLCE 32000 È Description of the display: NODEADDRESS The current device address as decimal and hexadecimal value. Stationmode , when configurating the AUMATIC as Basic Device.
Page 89
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus FF schedule list Dk FF-SCHEDULELIST AO DO PID DI AI 1 1 1 123 1234 Y N Y NYN YNYN È Description of the displays: FF-SCHEDULELIST The FF schedule list comprises the AUMATIC function blocks which can be called up within the AUMATIC due to a function block application configured by the user and loaded into the AUMATIC.
Page 90
For further references regarding the interpretation of the error codes shown, please refer to the “Manual (Device integration Fieldbus) AUMATIC AC 01.1/ACExC 01.1 Foun- dation Fieldbus". Any existing error is simultaneously shown via the hitherto existing status and diagnostic displays of the AUMATIC.
Page 91
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Troubleshooting 8.3.1 Problems with position feedback/indication E2 (from actuator) Ò Check FEEDBACK E2 M4101) parameter, page 27): Value must correspond to the installed position transmitter. Ò Check I/O1 ANALOG OUT1 M410A ) parameter: Value must correspond to wiring diagram.
Page 92
Actuator controls AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Manual Index Functions of the AUMATIC Output contacts Overrun (inner dead band) Actuator behaviour Actuator reaction I/O stack 2 Adaptive behaviour Identification Password change Alarm contact Indication lights Password entry Analogue output 1 feedback signals...
Page 93
Actuator controls Manual AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus Parameter index and display indications ADAPTIVE BEHAVIOUR OFF TIME CLOSE ALARM CONTACT OFF TIME OPEN EL. NAME PLATE ON TIME CLOSE EMERG.SEL.SW.POS. ON TIME OPEN EMERGENCY BEHAVIOUR BLINKER 21,26 OPEN POSITION...
Page 94
AUMA Polska Sp. z o.o. Europe AUMA Chile Respresentative Office PL-41-310 Dabrowa Górnicza CL-9500414 Buin AUMA Riester GmbH & Co. KG Tel +48 32 261 56 68 Tel +56 2 821 4108 Fax +48 32 261 48 23 Plant Müllheim Fax +56 2 281 9252 R.Ludzien@auma.com.pl...
Page 95
AUMA ACTUATORS (Singapore) Pte Ltd. Al-Arfaj Engineering Co WLL Australia SG-569551 Singapore KW-22004 Salmiyah BARRON GJM Pty. Ltd. Tel +65 6 4818750 Tel +965 481-7448 AU-NSW 1570 Artarmon Fax +65 6 4818269 Fax +965 481-7442 Tel +61 294361088 sales@auma.com.sg info@arfajengg.com Fax +61 294393413 www.auma.com.sg...
Page 96
AUMA Riester GmbH & Co. KG Postfach 1362 D-79373 Müllheim Tel +49 7631 809 - 0 Fax+49 7631 809 - 1250 riester@auma.com www.auma.com Certificate Registration No. Y004.513/003/en/1.08 12 100/104 4269 For detailed information on AUMA products refer to the Internet: www.auma.com...