AUMA SAExC 07.1 Operation Instructions Manual
AUMA SAExC 07.1 Operation Instructions Manual

AUMA SAExC 07.1 Operation Instructions Manual

Multi-turn actuator
Hide thumbs Also See for SAExC 07.1:
Table of Contents

Advertisement

Quick Links

Ex
Multi-turn actuator
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
with actuator controls
AUMATIC ACExC 01.1
Control:
Parallel
à Profibus DP
Profibus DP with FO
Modbus
Modbus with FO
DeviceNet
Foundation Fieldbus
Operation instructions
Assembly, operation, commissioning

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SAExC 07.1 and is the answer not in the manual?

Questions and answers

Summary of Contents for AUMA SAExC 07.1

  • Page 1 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Control: Parallel à Profibus DP Profibus DP with FO Modbus Modbus with FO DeviceNet Foundation Fieldbus Operation instructions Assembly, operation, commissioning...
  • Page 2: Table Of Contents

    Manual (Operation and setting) AUMATIC AC 01.0/ACExC 01.1 Profibus DP. Manual (Fieldbus device integration) AUMATIC AC 01.0/ACExC 01.1 Profibus DP. Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses from page 86). Table of contents Page Safety instructions .
  • Page 3 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Page 7.1.1 Status indication S0/S6 - operation 7.1.2 Status indication S4 - torque 7.2. Indication lights/LEDs 7.3. Mechanical position indicator/running indication (option) Signals .
  • Page 4: Safety Instructions

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Safety instructions 1.1. General notes on safety AUMA products are designed and manufactured in compliance with recog- Standards/directives nised standards and directives.
  • Page 5: Range Of Application

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 1.2. Range of application AUMA multi-turn actuators are designed for the operation of industrial valves, e.g. globe valves, gate valves, butterfly valves, and ball valves.
  • Page 6: Warnings And Notes

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 1.3. Warnings and notes The following warnings draw special attention to safety-relevant procedures in these operation instructions, each marked by the appropriate signal word (DANGER, WARNING, CAUTION, NOTICE).
  • Page 7: Identification

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Identification 2.1. Name plate Each device component (actuator, controls, motor) is equipped with a name plate. Figure 1 shows the arrangement of name plates on the device.
  • Page 8 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Identification data for explosion-proof version: Figure 4 0102 Riester GmbH & Co.KG D-79379 Muellheim II2G EEx de IIC T4...
  • Page 9: Short Description

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 2.2. Short description Definition in compliance with EN ISO 5210: Multi-turn actuator A multi-turn actuator is an actuator which transmits to the valve a torque for at least one full revolution.
  • Page 10: Transport, Storage And Packaging

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Transport, storage and packaging 3.1. Transport Ò For transport to place of installation, use sturdy packaging. Hovering load! DANGER Death or serious injury possible.
  • Page 11: Assembly

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Assembly 4.1. Handwheel fitting For transport purposes, handwheels from a diameter of 400 mm are sup- Information plied separately.
  • Page 12: Multi-Turn Actuator Mounting To Valve/Gearbox

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 4.2. Multi-turn actuator mounting to valve/gearbox 4.2.1 Output drive types B1, B2, B3, B4, B, and E For rotating, non-rising valve stem.
  • Page 13: Output Drive Type A

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 4.2.2 Output drive type A For rising, non-rotating valve stem. Application Capable of withstanding thrust Output drive type A as separate unit (figure 6):...
  • Page 14 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Mounting the multi-turn actuator (with output drive A) to valve Figure 7 Valve stem Valve flange Output drive type A...
  • Page 15: Accessories (Option)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 4.3. Accessories (option) 4.3.1 Protection tube for rising valve stem Figure 8 Cap for stem protection tube Sealing ring Stem protection tube 1.
  • Page 16: Mounting Positions Of The Local Controls

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 4.4. Mounting positions of the local controls The mounting position of the local controls is designed according to the order.
  • Page 17: Electrical Connection

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Electrical connection 5.1. General notes Danger due to incorrect electrical connection! WARNING Failure to observe this warning can result in death, serious injury, or prop- erty damage.
  • Page 18 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Only cables according to IEC 61158 and 61784 standards, cable type A, Bus cables may be used for Profibus DP wiring.
  • Page 19: Connecting Via Plug/Socket Connector With Screw-Type Terminals (Kp, Kph)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 5.2. Connecting via plug/socket connector with screw-type terminals (KP, KPH) Before mains connection Ò Check whether type of current, supply voltage, and frequency comply with motor data (refer to name plate at motor).
  • Page 20 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Connecting the cables 1. Remove cable sheathing in a length of 120 – 140 mm. 2. Strip wires: controls 8 mm, motor 12 mm.
  • Page 21 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Connecting bus cables 1. Connect bus cables (refer to figures 13 and 14). 2. If the actuator is the final device in the bus segment: Ò...
  • Page 22 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Closing the terminal compartment Refer to figure 15. 1. Clean sealing faces of housing and cover (1). 2. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
  • Page 23: Connecting Via Plug/Socket Connector With Spring Cage Terminals (Kes)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 5.3. Connecting via plug/socket connector with spring cage terminals (KES) Before mains connection Ò Check whether type of current, supply voltage, and frequency comply with motor data (refer to name plate at motor).
  • Page 24 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Connecting power cables 1. Remove cable sheathing. 2. Strip wires. 3. For stranded wires: use end sleeves according to DIN 46228.
  • Page 25 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Closing the terminal compartment Refer to figure 18. 1. Clean sealing faces at the cover and the housing.
  • Page 26: Accessories For Electrical Connection (Option)

    Permissible length of connecting cables for later separation of actuator and controls: max. 10 m. We recommend: AUMA cable set LSW21-KES or LSW22-KP. If not using an AUMA cable set, the following has to be observed as well: Use suitable flexible and screened connecting cables. –...
  • Page 27: Parking Frame

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 5.4.2 Parking frame Parking frame for safe storage of a disconnected plug. For protection against touching the bare contacts and against environmental influences.
  • Page 28: Operation

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Operation 6.1. Manual operation In case of motor failure or power failure, the actuator may be operated man- ually for purposes of setting and commissioning.
  • Page 29: Motor Operation

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 6.2. Motor operation Perform all commissioning settings prior to motor operation. 6.2.1 Local operation The local operation of the actuator is performed using the push buttons (figure 23).
  • Page 30: Menu Navigation Via Push Buttons (For Settings And Indications)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 6.3. Menu navigation via push buttons (for settings and indications) The push buttons of the local controls (figure 24) are used to view, edit, and show various indications on the display.
  • Page 31: Structural Design And Navigation

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 6.3.2 Structural design and navigation The indications on the display are divided into 3 groups: Group = status indications...
  • Page 32: Language Change In The Display

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 6.4. Language change in the display Æ Via the menu to parameter: MAIN MENU (M0) LANGUAGE/CONTRAST (M00) VIEW (M00)
  • Page 33 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Display indicates: EDIT M010 ‚ LANGUAGE LCD CONTRAST 7. Press Display shows the set value. EDIT M010 ‚...
  • Page 34: Indications

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Indications 7.1. Status indications in the display Status indications regarding faults and warnings, refer to page 58 et seqq.
  • Page 35: Status Indication S4 - Torque

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP CLOSED POSITION End position CLOSED reached. SETPOINT POSITION Setpoint (modulating actuators only). È Description of the fault indications: See page 58.
  • Page 36: Indication Lights/Leds

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 7.2. Indication lights/LEDs The indication lights/LEDs locally display the different operation states as optical signals. The assignment of signals is freely selectable.
  • Page 37: Signals

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Signals 8.1. Signals via fieldbus Feedback signals via Profibus DP can be configured. Configuration is defined via the GSD file only.
  • Page 38: Commissioning

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Commissioning Prior to any electrical operation (motor operation), ensure that all commis- sioning settings described in this clause have been performed.
  • Page 39: Type Of Seating: Check/Edit For End Positions

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 9.1. Type of seating: check/edit for end positions Valve damage due to incorrect setting! NOTICE Ò The type of seating must suit the valve.
  • Page 40 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Display indicates: SETTINGS ‚ SET LIMIT SWITCHES SEATING MODE TORQUE 5. Press Display indicates: SETTINGS SET LIMIT SWITCHES ...
  • Page 41 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Display indicates: SEATING MODE M111 VIEW EDIT 12. Press Display indicates: ENTER PASSWORD 0 * * * ...
  • Page 42: Torque Switching: Check/Set

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 9.2. Torque switching: check/set Valve damage due to incorrect setting! NOTICE Ò The torque must suit the valve.
  • Page 43 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 6. Press Display indicates: TORQUE M120 ‚ VIEW EDIT 7. Check settings (view): continue with 8. Change setting: continue with 11.
  • Page 44 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 13. Enter password: Press 4 times = 0000 (default factory password). Display indicates: EDIT M1210 EDIT M1211 ‚...
  • Page 45: Limit Switching Setting

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 9.3. Limit switching setting Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) SET LIMIT SWITCHES (M10)
  • Page 46 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 7. Setting end position CLOSED: continue with 8 Setting end position OPEN: continue with 13 Setting end position CLOSED 8.
  • Page 47 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP If an end position cannot be set: Information Ò Check the type of control unit in actuator. The end positions can be approached (via push buttons and selector switch Information in position LOCAL), even during motor operation.
  • Page 48: Bus Address Setting (Slaveaddress)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 9.4. Bus address setting (slaveaddress) Æ Via the menu to parameter: MAIN MENU (M0) SETTINGS (M1) PROFIBUS DP 1 (M1B)
  • Page 49 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Check settings (view) 8. Press Display indicates: PROFIBUS DP 1 M1B00 ‚ SLAVEADDRESS 9. Press Display indicates: VIEW...
  • Page 50 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Display shows the set value: EDIT M1B10 ‚ SLAVEADDRESS ¿:EDIT C:ESC 15. Press again to enter the edit mode.
  • Page 51: Test Run

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 9.5. Test run Perform test run only once all settings previously described in the Commis- sioning clause have been performed.
  • Page 52: Limit Switching Check

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions For actuators without indicator disc Ò Unscrew screw plug (1) and seal (2) or tube cap (4) and observe direc- tion of rotation at hollow shaft (3) or the stem (5).
  • Page 53: Switch Compartment: Open

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 9.6. Switch compartment: open The switch compartment must be opened to perform the following settings (options). Flameproof enclosure, danger of explosion! DANGER Risk of death or serious injury.
  • Page 54: Gear Stage Of The Reduction Gearing: Test/Set

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 9.8. Gear stage of the reduction gearing: test/set This test/setting is only required if the turns/stroke of the actuator have been changed at a later date.
  • Page 55 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Figure 29 Screw Crown wheel 4. Loosen screw (1). 5. Set crown wheel (2) to desired level according to table 6.
  • Page 56: Switch Compartment: Close

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 9.9. Switch compartment: close 1. Clean sealing faces of housing and cover. 2. Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
  • Page 57: Corrective Action

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Corrective action 10.1. Faults during commissioning 10.1.1 Mechanical position indicator Mechanical position indicator cannot be set. Fault description Actuator turns/stroke have been modified at a later date.
  • Page 58: Fault Indications And Warning Indications

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 10.2. Fault indications and warning indications Faults interrupt or prevent the electrical actuator operation. Warnings have no influence on the electrical actuator operation. They only serve for information purposes.
  • Page 59: Status Indication S1 - Faults

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 10.2.2 Status indication S1 - faults Faults are indicated in this group:  ‚ FAULT IND. NO FAULT È...
  • Page 60: Status Indication S2 - Warnings

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 10.2.3 Status indication S2 - warnings Warnings are indicated at this position.  ‚ WARNING IND. NO WARNING È...
  • Page 61 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Ò Check wiring. I/O1 ANALOG IN2 LOSS Loss of signal of the analogue input 2 of the parallel interface (only for fieldbus/standard interface combinations).
  • Page 62: Status Indication S3 - Causes For Not Ready Remote

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 10.2.4 Status indication S3 - causes for not ready remote The causes for the fault signals (status indication NOT READY IND.
  • Page 63: Fuses

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 10.3. Fuses Flameproof enclosure, danger of explosion! DANGER Risk of death or serious injury. Ò Before opening, ensure that there is no explosive gas and no voltage.
  • Page 64: Motor Protection (Thermal Monitoring)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 10.3.2 Motor protection (thermal monitoring) In order to protect against overheating and impermissibly high temperatures at the actuator, PTC thermistors or thermoswitches are embedded in the motor winding.
  • Page 65: Servicing And Maintenance

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Servicing and maintenance Damage caused by inappropriate maintenance! CAUTION Ò Servicing and maintenance tasks must be carried out exclusively by suit- ably qualified personnel authorised by the end user or contractor of the plant only.
  • Page 66: Disconnection From The Mains

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 11.2. Disconnection from the mains If the device must be demounted, e.g. for service purposes, it can be sepa- rated from the mains without having to remove the wiring.
  • Page 67: Maintenance

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP 11.3. Maintenance After 3 years at the latest for Ex certified products. Maintenance intervals In the factory, the gear housing is filled with grease.
  • Page 68: Disposal And Recycling

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 11.4. Disposal and recycling AUMA devices have a long lifetime. However, they have to be replaced at one point in time.
  • Page 69 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Notes...
  • Page 70: Spare Parts List

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Spare parts list 12.1. Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1...
  • Page 71 Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia- bility. Delivered spare parts may slightly vary from the representation.
  • Page 72: Controls Acexc 01.1 With Ex-Plug/Socket Connector With Terminal Board (Kp, Kph)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 12.2. Controls ACExC 01.1 with ex-plug/socket connector with terminal board (KP, KPH)
  • Page 73 Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia- bility. Delivered spare parts may slightly vary from the representation.
  • Page 74: Controls Acexc 01.1 With Ex-Plug-In Terminal Connection (Kes)

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 12.3. Controls ACExC 01.1 with ex-plug-in terminal connection (KES)
  • Page 75 Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia- bility. Delivered spare parts may slightly vary from the representation.
  • Page 76: Technical Data

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Technical data Features and functions of actuator Explosion protection Standard: II2G EEx de IIC T4 II2D Ex tD A21 IP6x T130°C...
  • Page 77 Protection cover, lockable Protection cover with indicator glass, lockable 2) Only partly possible in connection with process controller PID, please contact AUMA. 3) Not possible in combination with PTC tripping device 4) The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To reach the longest possible...
  • Page 78 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Functions Standard: Switch-off mode adjustable limit or torque seating for end position OPEN and end position CLOSED Torque monitoring over the whole travel...
  • Page 79 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Further options for Non-intrusive version with MWG in actuator Setting limit and torque switching via the local controls of the controls...
  • Page 80 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions Service conditions for actuator with controls Mounting position Any position Enclosure protection according Standard: IP 67 to EN 60 529...
  • Page 81: Certificates

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Certificates 14.1. Declaration of Conformity and Declaration of Incorporation...
  • Page 82: Ptb Certificate

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions 14.2. PTB certificate...
  • Page 83 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP...
  • Page 84 Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive with actuator controls AUMATIC ACExC 01.1 Profibus DP Operation instructions...
  • Page 85: Index

    Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive Operation instructions with actuator controls AUMATIC ACExC 01.1 Profibus DP Index Accessories for mounting Impedance Rated power 9,76 Assembly Indications Reduction gearing Indicator disc Reference documents Internet Running indication...
  • Page 86: Addresses

    Europe AUMA Polska Sp. z o.o. AUMA Automação do Brasil Ltda. PL-41-310 Dabrowa Górnicza BR-São Paulo AUMA Riester GmbH & Co. KG Tel +48 32 261 56 68 Tel +55 11 8114-6463 Plant Müllheim Fax +48 32 261 48 23 blitzco@uol.com.br...
  • Page 87 AUMA ACTUATORS (Singapore) Pte Ltd. Sunny Valves and Intertrade Corp. Ltd. SG-569551 Singapore TH-10120 Yannawa Bangkok Tel +65 6 4818750 Tel +66 2 2400656 Fax +65 6 4818269 Fax +66 2 2401095 sales@auma.com.sg sunnyvalves@inet.co.th www.auma.com.sg www.sunnyvalves.co.th/ AUMA Actuators Middle East W.L.L.
  • Page 88 AUMA Riester GmbH & Co. KG P.O. Box 1362 D-79373 Müllheim Tel +49 7631 809 - 0 Fax+49 7631 809 - 1250 riester@auma.com www.auma.com Certificate Registration No. Y004.592/003/en/1.10 12 100/104 4269 For detailed information on AUMA products refer to the Internet: www.auma.com...

This manual is also suitable for:

Saexc 16.1Sarexc 07.1Sarexc 16.1Aumatic acexc 01.1

Table of Contents