7.7.3 Proportional gain Kp setting

7.7.4 Reset time Ti setting

In case of an error variable, the P portion immediately (i.e. without delay)
changes the position value proportionally to the error variable.
If a small error variables already requires a major valve position adjustment,
the proportional gain Kp must be increased.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
PROPORT. GAIN Kp

:EDIT
Default value:
Setting range:
Information
If the reaction is too extreme (overshoot), the value must be reduced. If the
reaction is too weak, the value must be increased.
The reset time determines the I portion of the controller. The more inert a
system, the higher this value should be set.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
RESET TIME Ti

:EDIT
Default value:
Setting range:
Ò Increase Ti in case of propensity to oscillation
Information
Ò Decrease Ti if the reactions are excessively delayed
Ò Initial value for fast processes (pressure): 10
Ò Initial value for slow processes (temperature): 1000
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
PROCESS CONTROL PID (M1I)
PORPORT.GAIN Kp (M1I10)
M1I10
1.0
¿:OK C:ESC
1.0
to
0.1
10.0
PROCESS CONTROL PID (M1I)
RESET TIME Ti (M1I11)
M1I11
1000 s
¿:OK C:ESC
1000
s
1
to
1000
seconds