TRANSPORT cont.
Once fully out of the container position another piece of
timber the same size as the first piece of timber close to
the end being pulled so that the cooler will sit level for
fork lifting from the side of the cooler.

All models - Lifting/Positioning

Please review graphics for safe cooler lifting. The cooler
may be lifted either by fork-truck or crane with slings.
The method for lifting by crane is by lifting straps through
the cooler base fork-truck tyne openings. Do not attempt
to lift using any cabinet features or by retro-fitting lifting
lugs. The cabinet may be damaged and/or lift safety
compromised. It is recommended to use a spreader bar
on the straps or slings and to protect the upper edges of
the cooler from damage to the cabinet during the lift.

INSTALLATION

All models - Location/Site Preparation

Check the proposed cooler location to ensure that it is
structurally capable of supporting the weight of the cooler,
or provide an adequate alternate load bearing structure.
Model
CW-80
CW-80S
CW-80T
CW-80T-TWIN
Always locate the cooler where it will receive a plentiful
supply of fresh air, NOT in a recess where it may be
ILL2808-A
starved for air or where the air is polluted.
Air exiting the exhaust outlets is warm and heavily laden
with moisture. Ensure the exhaust air will not cause
corrosion or damage to other nearby items. Do not allow
exhaust air to re-circulate into the air intake of the cooler.
Allow clearances as illustrated below around the
perimeter of the product for maintenance access and to
ensure efficient performance.
Ensure that the location is a minimum of
• 3.0 m from a solid fuel heater flue,
• 1.5 m from a gas flue,
• 5.0 m from a sewer vent.
If the cooler is to be positioned on a concrete slab, the
minimum recommended sizes are:
CW-80 & CW-80S:
CW-80T:
CW-80T-TWIN:
CW-80, CW-80S
CW-80 & CW-80S
ILL2024-A
0.7m
CW-80T
CW-80T
ILL2025-A
INSTALLATION, OPERATION & MAINTENANCE MANUAL 866600CE-B | 11
Shipping Weight
Operating Weight
2000 kg
2100 kg
1955 kg
3910 kg
5.7 * 4.2 m
4.0 * 4.2 m
8.0 * 4.2 m
5.7m
CONCRETE SLAB
4.0m
1.0m
4.0m
CONCRETE SLAB
0.95m
2.3m
0.95m
3.0m
1.0m
ILL2288-A
2700 kg
2850 kg
2655 kg
5325 kg
0.95m
2.3m
4.2m
0.95m
ILL2209-A
ILL2209-A
4.2m
ILL2288-A