All Models - Standard Error Configuration - Seeley Climate Wizard CW-80 Installation & Operation Manual

Table of Contents

Advertisement

OPERATING INSTRUCTIONS
CW-80 - OPERATING SYSTEM cont.

All models - STANDARD Error Configuration

This error configuration is selected during commissioning for installations which prefer the cooler to go to vent mode
under most alarm conditions.
Item
1
One supply and / or one exhaust fan motor failure
2
Two or more supply and / or exhaust fan motor failures
3
Excessive pressure drop across air inlet filter pads - above
260Pa for more than 30 seconds
4
During pre-wet or normal sequential watering operation,
differential exhaust pressure across the core is inadequate
5
Initial filling of water tank to bottom probe takes more than
20 minutes to achieve.
6
Initial filling of water tank from bottom to mid probes takes
more than 20 minutes to achieve.
7
During pre-wet part A tank refilling to mid probe before
repeating core watering takes more than 10 minutes to
achieve.
8
During pre-wet part B water level recovery back to bottom
probe following a truncated watering period takes more than
10 minutes to achieve.
9
During pre-wet part B normal filling tank to mid probe takes
more than 20 minutes to achieve.
10
During normal run water level recovery back to bottom probe
following a truncated watering period takes more than 10
minutes to achieve.
11
During normal run normal filling tank to mid probe delays the
pump start by more than 5 minutes.
12
During normal run the average of the last 4 fill to mid probe
time periods has exceeded 2.5 minutes.
13
During normal run the average of the last 4 fill to mid probe
time periods has exceeded 90 seconds.
14
CW-80S ONLY
During Direct Only operation (without Indirect Cooling)
During normal filling tank to either top probe takes longer
than 20 minutes.
15
Water pump overload tripped.
Water pump overload tripped
Water pump overload tripped
16
Chlorinator power supply output
inadequate
Chlorinator power supply output
inadequate
Chlorinator power supply output
inadequate
28 |
CW-80 Container Cooler 866600CE-B
Event
Pump overload tripped.
Supply pump (Indirect
Core watering)
requested to run but
thermal overload has
tripped
CW-80S ONLY
Direct Water pump
requested to run but
thermal overload has
tripped.
Power supply output
inadequate
- For over 3 hours
- For over 5 days
Error
Error message on touch screen
Signal
"One supply and / or exhaust fan motor -
Critical
cooler will have reduced performance"
"Multiple supply and / or exhaust fan
Critical
motors - cooler has been shutdown"
"Air inlet filters pressure drop too high -
Warning
cooler will have reduced performance"
"Exhaust air pressure is too low - cooler
Critical
changed to vent mode"
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 1]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 2]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 3]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 4]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 5]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 6]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 7]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 8]
"Water supply - tank filling is slow - cooler
Warning
will have reduced performance" [code 10]
"Water supply - tank filling is too slow -
Critical
cooler changed to vent mode" [code 9]
"Watering system - pump overload tripped -
Critical
cooler shutdown"
"Watering system - pump overload tripped
- cooler shutdown" (CW-80, CW-80T, CW-
Critical
80T-TWIN) or "INDRCT PUMP" checked
(CW-80S)
Critical
Direct Pump checked
Warning
"Chlorinator - low power supply output"
Warning
"Preliminary warning" checked
(pulsed)
Critical
"Cooler has shutdown checked"
Action
Notification
Shutdown
Notification
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Change to
vent mode
Notification
Change to
vent mode
Shutdown
Shutdown
Shutdown
Notification
Shutdown