APPENDIX A BACnet PROGRAMMING INFORMATION cont.
BACnet Object List CW-80 Series
V4 28-07-2016
Application: - Customer
Read Only (R)
BACnet Object Properties
Object-name
R1. Basic
Software - Id Number And Version
Software - Date
Control Mode Status - Off
Control Mode Status - Man
Control Mode Status - Local Auto
Control Mode Status - BMS Auto
Current Auto Op Status - Standby
Current Auto Op Status - Vent
Curr Auto Op Status - Indir Cooling
Curr Auto Op Status - Dir Cooling
WtrSqCtr - Fill Tnk To Top Lvl Sen
WtrSqCtr - Start Exh Fans Start
Chlor
WtrSqCtr - Pre-Wet Indirect Cores
WtrSqCtr - Normal Seq Wtr Of Ind
Core
WtrSqCtr - Direct Only Operation
WtrSqCtr - Vent Mode Del Tank
Drain
WtrSqCtr - Standby Mode Del
Tank Drn
WtrSqCtr - Shutdown
Commissioning Mode
Page 2 of 5
Object-identifier
Object-type
Analogue-input 17
Analogue-input Decimal AAABB, AAA = ID number (0 to 320), BB = version (01 to 99)
Analogue-input 18
Analogue-input Decimal ABBCC, A not used, BB = week number (1 to 53),
Binary-input 19
Binary-input
Binary-input 20
Binary-input
Binary-input 21
Binary-input
Binary-input 22
Binary-input
Binary-input 23
Binary-input
Binary-input 24
Binary-input
Binary-input 25
Binary-input
Binary-input 26
Binary-input
Binary-input 27
Binary-input
Binary-input 28
Binary-input
Binary-input 29
Binary-input
Binary-input 30
Binary-input
Binary-input 31
Binary-input
Binary-input 32
Binary-input
Binary-input 33
Binary-input
Binary-input 34
Binary-input
Binary-input 35
Binary-input
CC = year (00 to 99 - lower 2 digits of year number)
Active = current active control mode as selected from touch screen
One only digital signal will be active at a time
Standby
Active = current operating status
All inactive implies cooler not running or
Ventilation
control set to "off" or "manual"
Indirect cooling (no added
Possible to have both indirect and direct
water vapour)
cooling active at the same time (CW-
Direct cooling (adds water
80S only)
vapour - CW-80S only)
Initial filling of tank to top
Active = the current stage of the
level sensor
watering sequence control in auto
operation (local auto or BMS auto)
Start exhaust fans and start
chlorinator (as appropriate)
Only one digital signal will be active at
a time
pre-wet indirect cores in
preparation for indirect
All inactive implies cooler not running or
cooling
control set to "off" or "manual"
Normal ongoing sequential
watering of indirect cores -
may be in conjunction with
watering of direct cores (CW-
80S only)
Watering of direct cores only
(CW-80S only)
Delayed tank drain whilst
cooler in ventilation mode
Delayed tank drain whilst
cooler in standby mode
Shutdown and tank drain
following expiry of tank drain
delay
Active = factory input X24 has been disconnected to invoke
commissioning mode
INSTALLATION, OPERATION & MAINTENANCE MANUAL 866600CE-B | 45