MAINTENANCE INSTRUCTIONS cont.

All models: Inlet Solenoid Valve

All models - Inlet Ball Valve

36 |
CW-80 Container Cooler 866600CE-B
All models - Distributing Valve
Open the access door at the control end of the cooler to
gain access to the Distributing Valve.
1.
Turn the cooler controller off and then the mains
power isolation switch off.
2.
The Distributing Valve is located below the
electronics control box.
ILL3094-A
ILL3095-A
3.
If the Distributing Valve is worn and fails to function
correctly the valve can be refurbished by replacing
the internal sealing components and indexing cam
assembly. Remove the 7 off phillips head screws at
top of valve. Remove the top cover and the internal
plunger. Replace with new components and re-
assemble.
ILL2229-A
ILL2378-A