INSTALLATION cont.
Position the complete weatherseal assemblies over
exhaust fans as per the illustration below.
Use 4 off M8 screw assembly A to fasten each Weather
Seal Assembly as per the illustration below.
18 |
CW-80 Container Cooler 866600CE-B
ILL2304-A
ILL2304-A
SCREW
ASSEMBLY
"A"
ILL2223-A
ILL2223-A
ILL2042-A

All models - Water Supply Installation

The cooler requires a permanent water supply to be
connected. Installation of the water supply to the cooler
must conform to local plumbing rules, regulations and
standards.
The following specifications for water supply are required:
Water Supply:
3/4" male BSPT connection, Min. 45 LPM @ 85 Kpa.
Recommended pressure range 200 to 500 Kpa.
Maximum pressure (static) 800 Kpa
Water Supply Temperature:
Max. 40°C
Water Supply Salinity:
100 - 1150 μs/cm
Note! For the CW-80T-TWIN, there is a requirement for 2
connections, one at each end.
In areas subject to freezing, the water line needs a drain
down facility.
If the water pressure exceeds this maximum specification
then a pressure reducing valve is required and must be
supplied and fitted by the Installer.

WATER SUPPLY FILTRATION

Seeley International requires an inlet filter to be installed
on the water supply line, external to the Climate Wizard
cooler to prevent any debris from entering and damaging
cooler components.
Important! Flush the water pipe to remove any
contaminants (swarf, filings or dirt) before final fitting.
Contaminants can lodge in the solenoid, preventing it
from functioning correctly.
Climate Wizard's water management system is
designed to use water that is suitable to be classified as
'potable' and fit for human consumption. If alternative
water (including rain water) is to be used that contains
high levels of salinity, hardness, acidity or chemical
contaminants, then additional filtration or treatment
systems should be employed to render the water
'potable'.

WATER HAMMER

Not all installation pipeworks are the same, and some
may require additional prevention against water hammer.
If water hammer is a problem, it is the responsibility of
the Installer to fit an appropriate water hammer arresting
device external to the cooler.