APPENDIX A BACnet PROGRAMMING INFORMATION cont.
BACnet Object List CW-80 Series
V4 28-07-2016
Application: - Customer
Read Only (R)
BACnet Object Properties
Object-name
R10. Errors - Continued
WtrSup Er- Unac Avg Tnk Refill
Time
WtrSup Er- Tnk Fil Top Lvl Sen Dir
Pump Error
Direct Pump Error
Supply fan Sf01 Error
Supply fan Sf02 Error
Exhaust fan Ef01 Error
Exhaust fan Ef02 Error
Exhaust fan Ef03 Error
Exhaust fan Ef04 Error
Chlorinator Warning Error
Chlorinator Critical Error
High Filter Pa Warning
Exhaust Pa error
Forced Vent Mode Due To Error
Forced Shutdown Mode Due To
error
48 |
CW-80 Container Cooler 866600CE-B
Page 5 of 5
Object-identifier
Object-type
Binary-input 92
Binary-input
Binary-input 93
Binary-input
Binary-input 94
Binary-input
Binary-input 95
Binary-Input
Binary-input 96
Binary-Input
Binary-input 97
Binary-input
Binary-input 98
Binary-input
Binary-input 99
Binary-input
Binary-input 100
Binary-input
Binary-input 101
Binary-input
Binary-input 102
Binary-input
Binary-input 103
Binary-input
Binary-input 104
Binary-input
Binary-input 105
Binary-input
Binary-input 106
Binary-input
Binary-input 107
Binary-input
Details
Active = unacceptably long average tank refill time period encountered
during normal sequential watering - error flag set and appropriate action
taken (PLC code #8)
Active = unacceptably long time period encountered to fill or refill tank
to top level sensor during direct only cooling operation (supercool only)
- error flag set and appropriate action taken (PLC code #9)
Active = error flag set because the indirect pump motor overload has
tripped
Active = error flag set because the direct pump motor overload has
tripped (CW-80S only)
Active = fan error flag set because power has been applied to the
associated fan but an ok signal has not been received within a specified
time
Active = warning flag set because
DC output has been inadequate >
3 hours
Active = error flag set because DC
output has been inadequate > 5
days
Active = warning flag set because
pressure across inlet filters is too
high
Active = error flag set because
exhaust pressure across core is
too low
Active = unit operating in vent
mode - possibly contrary to other
control requests
Active = unit has been shut down
- possibly contrary to other control
Requests
These errors are generated whilst
the cooler is operating in automatic
(local or BMS) mode