INSTALLATION cont.
All models - Drain Installation
Climate Wizard coolers require a permanent drain to be
connected.
A built-in Drain Valve is controlled by the Water
Management System. Drain water is high in salinity and
must be carried away to a suitable discharge point in
accordance with local regulations.
Drain Rate:
40 LPM
The drain outlet provided accepts an NPS 2 (60.35mm
OD (DN50) to ASTM D1785) PVC pressure water pipe.

All models - Electrical Supply Installation

(Aust/Eur 3 Phase, 380 - 415V 50Hz)
Installation of the cooler must conform to local electrical
rules, regulations and standards.
It is a requirement of Seeley International that all coolers
be wired with a dedicated circuit and circuit breaker to the
distribution board.
A mains isolation switch shall be furnished by the
contractor and installed adjacent to the cooler. (Note!:
This isolator is already included as part of the factory
build for model CW-80T-TWIN).
Coolers require a 3-phase neutral and earth electrical
power to be supplied. Minimum 3-wire + ground
conductors supplied from an independent circuit breaker.
CW-80 and CW-80T Electrical Supply Specification:
Standard: 3 phase N+E, 380-415V 50Hz 22A
High Capacity: 3 phase N+E, 380-415V 50Hz 27A
CW-80S Electrical Supply Specification:
Standard: 3 phase N+E, 380-415V 50Hz 22A
ILL2563-A
High Capacity: 3 phase N+E, 380-415V 50Hz 27A
Mains power terminals are provided inside the electrical
cabinet with gland plate provided for cable entry.
ILL2565-A
ILL2565-A
INSTALLATION, OPERATION & MAINTENANCE MANUAL 866600CE-B | 19