INSTALLATION

UNPACKING THE COOLER

Inspect for transport damage prior to installation.
The cooler will be delivered wrapped in plastic film with
timber dunnage, all of which will need to be removed before
installation.
Place the control items shown below aside for later connection.
REMOVE TIE DOWN HOOKS AWAY FROM LIFTING POINTS.
DO NOT LIFT COOLER USING THE TIE DOWN HOOKS.

LIFTING AND MOVING THE COOLER

ILL3508-A
The cooler may be lifted either by fork-truck or by crane.
DO NOT SLING COOLER.
Lifting points for "D" shackles are provided for crane lifting.
These eyelets are located at the top corners of the cooler.
Ensure appropriately rated shackles are used.
Do not lift using any cabinet features or by retro-fitting lifting
lugs. The cabinet may be damaged and/or lift safety may be
compromised.
|
CW-P15 Indirect Evaporative Cooler 859740-G
9
Moving the cooler using Forklift Tyne slot openings.

COOLER LOCATION

Check the proposed cooler location, to ensure that it is
structurally capable of supporting the weight of the cooler, or
provide an adequate alternate load bearing structure.
Always locate the cooler where it will receive a plentiful supply
of fresh air, NOT in a recess where it may be starved for air or
where the air is polluted.
Air exiting the exhaust duct is warm and heavily laden with
moisture. Ensure the cooler's exhaust outlet location will not
cause corrosion or damage to other nearby items. Do not allow
exhaust air to re-circulate into the air intake of the cooler.
Ensure the location is a minimum of:
ILL2260-A
• 3.0m (10') from a solid fuel heater flue,
• 1.5m (5') from a gas flue,
• 5.0m (16') from a sewer vent
• Rear = Min 1.5m (5') from a wall
Allow adequate access to the inlet and outlet sides of cooler for
maintenance. Coolers may be arrange side by side or on top
of each other via a suitable frame. Provision must be made for
access to electricity, water supplies and drains.
ILL2364-A
Note! Do you need to discuss the installation of items like
safety anchor points with the customer?
ILL2264-A
ILL3506-A

DRIP-TRAY

When Climate Wizard coolers are installed indoors, or
anywhere that water leakage could cause damage, install a
corrosion resistant drip tray under the whole machine.
Recommended size
CW-P15 - 1500w x 2000d x 50h mm (59"w x 79"d x 2"h)
Apply silicone sealant between drip-tray and cooler base at
every fixing.
ILL2262-A
ILL2261-A
ILL2261-A
ILL2984-A