APPENDIX B. COMMISSIONING cont.
SCHEDULE OF SET POINTS
BACnet information is provided within this table.
Item
Air filter differential pressure switch
Salinity manager auto drain salinity threshold
Omron K8AK-pm2
Selectable start delay in seconds
Selectable basic voltage setting
Selectable Phase to Neutral Voltage
Over voltage %
Under voltage %
Recovery time in seconds
FX
u-485ADP-MB terminating resistor
3
Protonode BACnet gateway MAC address
Protonode BACnet gateway Baud rate
Protonode BACnet gateway Field protocol
Protonode BACnet gateway
Modbus RS485 biasing - 2x red jumpers
Protonode BACnet gateway
Modbus RS485 end of line switch - blue jumper
Protonode BACnet gateway
BACnet RS485 end of line switch - slide
Protonode BACnet gateway
IP address
Subnet Mask
Pump overload: Indirect
Pump overload: Direct (CW-80S Supercool only)
Supply Fan De-rating %
Supply Fan De-rating % (CW-80S Supercool only)
Controller Error Actions
Control screen display units
54 |
CW-80 Container Cooler 866600CE-B
Setting range
20 to 300 Pa
1250 ppm to 2850 ppm
(Dip switch #1 to #5)
1 s or 5 s
PH-PH or PH - N
220, 230, 240, 277V
-30% to +25%
-30% to +25%
0.1 to 30 s
330, 110 ohms, open
A0
1 to 255
A1
A2
A3
A4
A5
A6
A7
B0
9600 to 76800
B1
B2
B3
S0
BACnet / IP;
BACnet MS / TP;
S1
Metasys N2;
Modbus TCP / IP
S2
S3
Biasing, no biasing
ON, OFF
ON, OFF
Various, as IP rules
1.0 to 1.6 A
0.63 to 1.0 A
40 - 100%
40 - 100%
Standard or Critical
Metric or Imperial
Actual setting
Comments
260 Pa
Same as all
other Coolers
1250 ppm
without BACnet
(Dip switch #1)
1 s
PH - N
240V
+10%
-15%
10 s
Open
Applicable to
BACnet only
ON
3
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
38400
ON
OFF
ON
ON
BACnet MS / TP
OFF
OFF
OFF
No biasing
(Factory Default)
OFF (Factory Default)
OFF (Factory Default)
192.168.1.24
255.255.255.0 (Factory
Default)
1.6 A
Same as all
other Coolers
0.79 A
without BACnet
80% (Factory Default)
85% (Factory Default)
Standard (Factory
Default)
Metric (Factory Default)