APPENDIX A BACnet PROGRAMMING INFORMATION cont.
BACnet Object List CW-80 Series
V4 28-07-2016
Application: - Customer
Read Only (R)
BACnet Object Properties
Object-name
R6. Tank
Top Tank Level Sensor
Bottom Tank Level Sensor
Inlet Solenoid Valve
Drain Valve
Avg Tank Fill Time
Chlorinator Enable
Chlorinator Output
Drain Delay Minute Counter
R7. Watering System
Indirect Pump Run
Direct Pump Run
R8. Salinity
Salinity High
Salinity Drain In Operation
R9. Hours
Hour Meter - Overall Cooler Run
Hour Meter - Supply Fans
Hour Meter - Exhaust Fans
Hour Meter - Indirect Pump
Hour Meter - Direct Pump
Hour Meter - Chlorinator
R10. Errors
Water Supply Wrn - Exc Avg Tnk
Ref Tm
WtrSup Er- Tank Fill To Bot Lvl
Sen
WtrSup Er- Tank Fill To Top Lvl
Sen
WtrSup Er- Tnk Refl Top Lvl
SenPreWtA
WtrSup Er- Tnk Refl Bot Lvl
SenPreWtB
WtrSup Er- Tnk Refl Top Lvl
SenPreWtB
WtrSup Er- Tnk refl Bot Lvl
SenSeqWtr
WtrSup Er- Tnk Refl Top Lvl
SenSeqWr
Page 4 of 5
Object-identifier
Object-type
Binary-input 66
Binary-input
Binary-input 67
Binary-input
Binary-input 68
Binary-input
Binary-input 69
Binary-input
Analogue-input 70
Analogue-input Average inlet solenoid on time required to refill the tank in seconds for
Binary-input 71
Binary-input
Binary-input 72
Binary-input
Analogue-input 73
Analogue-input Drain delay elapsed period in minutes - tank drains after 4320 minutes
Binary-input 74
Binary-input
Binary-input 75
Binary-input
Binary-input 76
Binary-input
Binary-input 77
Binary-input
Analogue-input 78
Analogue-input Range 0 to > 2x10^9
Analogue-input 79
Analogue-input Range 0 to > 2x10^9
Analogue-input 80
Analogue-input Range 0 to > 2x10^9
Analogue-input 81
Analogue-input Range 0 to > 2x10^9
Analogue-input 82
Analogue-input Range 0 to > 2x10^9 (CW-80S
Analogue-input 83
Analogue-input Range 0 to > 2x10^9
Binary-input 84
Binary-input
Binary-input 85
Binary-input
Binary-input 86
Binary-input
Binary-input 87
Binary-input
Binary-input 88
Binary-input
Binary-input 89
Binary-input
Binary-input 90
Binary-input
Binary-input 91
Binary-input
Active = tank water above top level sensor located in central chamber
Active = tank water above bottom level sensor located in central
chamber
Active = inlet solenoid valve open
Active = tank drain valve open
the last 4 refills during normal sequential watering
Active = mains power being applied to chlorinator power supply
Active = chlorinator power supply variable DC output voltage is at an
acceptable level
(3 days) in vent or standby modes
Active = indirect pump run to irrigate indirect cores (cooling without
adding water vapour)
Active = direct pump run to irrigate direct media (cooling with adding
water vapour - CW-80S only)
Active = high salinity signal being received from water manager
Active = timed drain in progress in response to high salinity
only)
Active = poor water supply is resulting in excessive average tank refill
time during normal sequential watering and also causing reduced
cooling performance - warning flag set and cooler continues operation
(PLC code #10)
Active = unacceptably long time period encountered to fill tank from
empty to bottom level sensor during initial tank filling - error flag set and
appropriate action taken (PLC code #1)
Active = unacceptably long time period encountered to fill tank from
bottom level sensor to top level sensor during initial tank filling - error
flag set and appropriate action taken. (PLC code #2)
Active = unacceptably long time period encountered to refill tank to top
level sensor during pre-wet part A - error flag set and appropriate action
taken. (PLC code #3)
Active = unacceptably long time period encountered to refill tank
to bottom level sensor during pre-wet part B - error flag set and
appropriate action taken (PLC code #4)
Active = unacceptably long time period encountered to refill tank to top
level sensor during pre-wet part B - error flag set and appropriate action
taken (PLC code #5)
Active = unacceptably long time period encountered to refill tank to
bottom level sensor during normal sequential watering - error flag set
and appropriate action taken
Active = unacceptably long time period encountered to refill tank to
top level sensor during normal sequential watering - error flag set and
appropriate action taken (PLC code #7)
INSTALLATION, OPERATION & MAINTENANCE MANUAL 866600CE-B | 47
Details
Total associated accumulated
running time in hours
(PLC code #6)