Alarm Relay (Do Type=1)+ Buzzer Activated; Relay + Buzzer Activated; It Follows Its Regulation - Emerson Dixell iProChill IPC115D Application Manual

Table of Contents

Advertisement

Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Compressors
Pump down solenoid valve
10.28 EVAPORATOR WATER PUMP OVERLOAD ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Evaporator water pump
Condenser water pump
Compressors
Pump down solenoid valve
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx

It follows its regulation

it follows its regulation
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Off with manual reset alarm
It follows its regulation
AtE1 (evaporator n° 1 water pump overload alarm)
AtE2 (evaporator support n° 2 water pump overload alarm)
Evap.pump 1 overl
Evap.pump 2 overl
DI configured as Evaporator main pump / Supply fan Overload (DI type=56)
active and par CF01≠0.
DI configured as Evaporator support pump Overload (DI type=57) active.
With DI not active
Manual. (reset procedure in functions menu)
flashing

Alarm relay (DO type=1)+ buzzer activated

Relay + buzzer activated

It follows its regulation
it follows its regulation
it follows its regulation
it follows its regulation
It follows its regulation
Off if no pump is available
Off if no pump is available
It follows its regulation
Off if pump is available
It follows its regulation
Off if pump is available
Off if pump is available
iProCHILL
190/205