AEM1 ...AEM4 (IPROEX60D 1... IPROEX60D 4 not connect alarm)
E1 discon...E4 discon
The expansion IPROEX60D IO (AI/DI/AO/DO) is used and lose communication
by can bus.
IPROEX60D IO is disabled or communication is recovered.
Automatic
flashing
Alarm relay (DO type=1) + buzzer activated
Relay + buzzer activated
Off
APS (Phases sequence alarm)
Phases sequ AL
Digital input Phase sequence relay (DI type=113) active.
Digital input Phase sequence relay deactivate.
Manual
flashing
Alarm relay (DO type=153) + buzzer activated
Relay + buzzer activated
Off
AFFC (Anti-freeze alarm in free-cooling)
Antif AL FC
FC01 = 4, During free-cooling working if External air temperature NTC
temperature probe (free-cooling) (AI type=34) value <= set FC07 for FC24
times. AFFC alarm will be signal after a delay of AL67.
External air temperature >= set FC07 + differential FC08.
Automatic – becomes manual after AL68 interventions/hour.
flashing
Alarm relay (DO type=1) + buzzer activated
Relay + buzzer activated
Follow their regulation