10.7 LOW CONDENSATION TEMPERATURE/PRESSURE ALARM (IF THE EVAPORATOR
PRESSURE PROBES ARE NOT CONFIGURED)
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Compressors
Pump down solenoid valve
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
b1lp-...b4lp (circuit n° 1-...circuit n° 4 condensation low temp/pressure alarm)
Low press circuit1-...Low press circuit4
The alarm is activated when the probe configures as condensation control
probes (AI type=48...55) < AL03 set in the following conditions. And
evaporator pressure probes (AI type=56...59) are not configured.
working in cooling or heating mode
stand-by or OFF-remote if AL08 = 1
In defrost if AL06=1
The alarm is not signalled:
in defrost for time AL07 in correspondence with valve inversion
on compressor switch-on for the time AL01
If the condensation control probe's temperature/pressure > AL03 + differential
AL04
Automatic – it becomes manual after AL05 interventions/hour (reset procedure
in functions menu)
flashing
Alarm relay + buzzer activated
Relay + buzzer activated
it follows its regulation
it follows its regulation
it follows its regulation
It follows/they follow its/their regulation
It follows its regulation
It follows its regulation
Off
It follows its regulation
It follows its regulation
Off
off