Emerson Dixell iProChill IPC115D Application Manual page 123

Table of Contents

Advertisement

ST 22
Circuit 2 heat pump temperature control probe
0 - evaporator input NTC
1 - Evaporator output 1 NTC
2 - Evaporator output 2 NTC
3 - Evaporator output 3 NTC
4 - Evaporator output 4 NTC
5 - Evaporator common output NTC
8 - condenser water common input NTC
9 - circuit 1 condenser water input NTC
10 - circuit 2 condenser water input NTC
11 - circuit 3 condenser water input NTC
12 - circuit 4 condenser water input NTC
13 - circuit 1 condenser water output NTC
14 - circuit 2 condenser water output NTC
15 - circuit 3 condenser water output NTC
16 - circuit 4 condenser water output NTC
17 - condenser water common output NTC
Parameter
Description
ST 23
Circuit 1 band offset
ST 24
Circuit 1 integral sampling time
ST 25
Circuit 1 derived sampling time
ST 26
Circuit 2 band offset
ST 27
Circuit 2 integral sampling time
ST 28
Circuit 2 derived sampling time
ST 29
Activation offset with regulation of the neutral zone
When the controlled temperature (coming from neutral zone) enters the
compressors activation zone the compressors/capacity steps are enabled
only if the variable exceeds (in cooling) or drops below (in heating) the
relevant threshold for at least ST30.
ST 30
Activation delay with regulation of the neutral zone
The controlled variable must be over (in cooling) or under (in heating) the
above mentioned activation level for at least the ST30 time before the
compressor/capacity step is switched ON.
ST 31
Deactivation offset with regulation of the neutral zone
When the controlled temperature (coming from neutral zone) enters the
compressors disabling zone the compressors/capacity steps are disabled
only if the variable drops below (in cooling) or exceeds(in heating) the
relevant threshold of at least ST32.
ST 32
Deactivation delay with regulation of the neutral zone
The controlled variable must be under (in cooling) or over (in heating) the
above mentioned activation level for at least the ST32 time before the
compressor/capacity step is switched OFF.
Parameter
Description
DP1
Row 1 of Visograph keyboard 1 analogue input display
0 = no display (the line remains empty), others are same with probe
configuration
DP2
Row 2 of Visograph keyboard 1 analogue input display
0 = no display (the line remains empty) , others are same with probe
configuration
DP3
Row 3 of Visograph keyboard 1 analogue input display
0 = no display (the line remains empty) , others are same with probe
configuration
DP4
Row 4 of Visograph keyboard 1 analogue input display
0 = no display (the line remains empty) , others are same with probe
configuration
DP12
HMI type (Can be seen only in Wizmate by Administrator).
0 = Visograph 1
1 = Visograph 2
2 = Visotouch
For visograph 2 and Visotouch:
Leds green: always on;
Leds red: on when alarm active or resettable
Parameter
Description
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
Circuit 1 PID regulation
Circuit 2 PID regulation
Displays
Remote terminal 1
Configuration
Unit
0
17
min
max
um
Resolution
-25.0
25.0
°C
Dec
-45
45
°F
int
0
250
Sec
0
250
Sec
-25.0
25.0
°C
Dec
-45
45
°F
int
0
250
Sec
0
250
Sec
0.0
25.0
°C
Dec
0
45
°F
Int
0
250
Sec
0.0
25.0
°C
Dec
0
45
°F
Int
0
250
Sec
min
max
um
Resolution
0
66
0
66
0
66
0
66
0
2
min
max
um
Resolution
iProCHILL
123/205

Advertisement

Table of Contents
loading

Table of Contents