10.29 CONDENSER WATER PUMPING OVERLOAD ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Evaporator water pump
Condenser water pump
Compressors
Pump down solenoid valve
10.30 GENERIC ALARM 1
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Other loads
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
AtC1 (condenser n° 1 water pump overload alarm)
AtC2 (condenser support n° 2 water pump overload alarm)
Cond.pump 1 overl
Cond.pump 2 overl
DI configured as Condenser main pump Overload (AI type=58) active.
DI configured as Condenser support pump Overload (AI type=59) active.
With DI not active
Manual.
flashing
Alarm relay (DO type=1) + buzzer activated
Relay + buzzer activated
It follows its regulation
it follows its regulation
it follows its regulation
it follows its regulation
It follows its regulation
Off if no pump is available
Off if no pump is available
It follows its regulation
It follows its regulation
Off if no pump is available
Off if no pump is available
Off if no pump is available
ALc1 (Generic alarm 1)
Generic AL1
DI configured as Generic alarm 1 digital input (DI type=89) active for the time
set in the Par AL54
DI configured as Generic alarm 1 digital input (DI type=89) not active for the
time set in the Par AL55
Automatic – becomes manual after AL53 interventions/hour. It is recorded in
the historical alarms only with manual reset
flashing
Alarm relay (DO type=166) + buzzer activated
Relay + buzzer activated
Off