Emerson Dixell iProChill IPC115D Application Manual page 128

Table of Contents

Advertisement

CO 18
Balance/saturation criteria
0= Hours
1= Starts
CO 19
Not used
CO 20
Not used
CO 21
Not used
CO 22
Not used
CO 23
Not used
CO 24
Not used
CO 25
Not used
CO 26
Not used
CO 27
Not used
CO 28
Not used
CO 29
Not used
CO 30
Not used
CO 31
Not used
CO 32
Not used
CO 33
Not used
CO 34
Not used
CO 35
Maximum n° of compressor starts after 15 minutes ON
0 = function disabled
CO 36
Max time with no resources being inserted with at least one resource active
CO 37
Max time in a neutral zone with no resources rotating
CO 38
Maximum continuous working time for individual compressor in the circuit.
CO 39
Compressor operation time at maximum speed requested by temperature
control
0 = function is disabled
CO 40
Minimum value for digital scroll 0-10V analogue output at peak
CO 41
Power implementation interval at peak
CO 42
Determines the minimum continuative operation percentage of the
modulating compressor below which the CO43 time count starts
0 = function is disabled
CO 43
MAX continuative operation time of modulating compressor with
operation percentage below CO42
0 = function is disabled
CO 44
Forced working time at maximum speed
CO 45
Maximum continuative operation time of modulating compressor after
which the modulating compressor is switched off and insertion of another
compressor is forced depending on rotation
0 = function is disabled
CO 46
Minimum value for circuit 1 inverter 0-10V analogue output
CO 47
Maximum value for circuit 1 inverter 0-10V analogue output
CO 48
Minimum value for circuit 2 inverter 0-10V analogue output
CO 49
Maximum value for circuit 2 inverter 0-10V analogue output
CO 50
Normal power implementation interval
CO 51
Activation set point of the liquid injection solenoid valve
CO 52
Differential deactivation of the liquid injection solenoid valve
CO 53
Set compressor 1 hour meter (see chap. maintenance request function)
CO 54
Set compressor 2 hour meter (see chap. maintenance request function)
CO 55
Set compressor 3 hour meter (see chap. maintenance request function)
CO 56
Set compressor 4 hour meter (see chap. maintenance request function)
CO 57
Set compressor 5 hour meter (see chap. maintenance request function)
CO 58
Set compressor 6 hour meter (see chap. maintenance request function)
CO 59
Set compressor 7 hour meter (see chap. maintenance request function)
CO 60
Set compressor 8 hour meter (see chap. maintenance request function)
CO 61
Set compressor 9 hour meter (see chap. maintenance request function)
CO 62
Set compressor 10 hour meter (see chap. maintenance request function)
CO 63
Set compressor 11 hour meter (see chap. maintenance request function)
CO 64
Set compressor 12 hour meter (see chap. maintenance request function)
CO 65
Set compressor 13 hour meter (see chap. maintenance request function)
CO 66
Set compressor 14 hour meter (see chap. maintenance request function)
CO 67
Set compressor 15 hour meter (see chap. maintenance request function)
CO 68
Set compressor 16 hour meter (see chap. maintenance request function)
CO 69
Delay time in enabling Refcomp Inverter compressor relay based on
temperature control request
CO 70
Delay in VI valves activation from compressor start-up
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
Resource control in proportional/neutral zone mode
Compressor in tandem forced rotation function
Compressor with modulating control
Compressors liquid injection function
Loads maintenance
0
1
0
15
0
250
Min
0
999
Hr
0
250
Min
0
250
Sec
0
100
%
0
250
Sec
0
100
%
0
250
Min
0
250
Sec
0
999
Hr
0
CO47
%
CO46
100
%
0
CO49
%
CO48
100
%
1
250
Sec
-50.0
150.0
°C
-58
302
°F
0.1
25.0
°C
0
45
°F
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
999
Hr
0
250
sec
0
250
sec
iProCHILL
10 Min
1Hr
10 Min
10sec
1Hr
Dec
int
Dec
int
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
10 Hr
128/205