Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Affected circuits
compressors
Unaffected circuits
compressors
Unaffected circuits pump
down solenoid valve
Affected circuits pump
down solenoid valve
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
it follows its regulation
It follows/they follow its/their regulation
It follows its regulation
It follows its regulation
If the Par. FA02= 0 fan working mode dependent on the compressor. With
alarm active the fans are forced to maximum speed for 60 seconds before
switching-off
If the Par. FA02= 1 fan working mode independent from the compressor. With
alarm active the fans are forced to maximum speed for 60 seconds and then
follow their regulation
It follows its regulation
It follows its regulation
Off
It follows its regulation
It follows its regulation
off
iProCHILL
172/205