Compressors not affected
Pump down solenoid valve
10.18 COMPRESSOR HIGH DISCHARGE TEMPERATURE ALARM FROM ANALOGUE INPUT
Reset
Reset
Compressor affected
Compressor not affected
Liquid
injection
solenoid
valve
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
If Par. AL29 = 0 following their regulation
If Par. AL29 = 1 off
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
C1dt...C16dt (compressor n° 1...16 high discharge temperature alarm)
Hi Disch temp.C1...Hi Disch temp.C16
The temperature measured by the probe configured as Compressor 1...16
PTC discharge temperature probe (AI type=1...16) >= AL50 set
The temperature measured by the probe configured as Compressor 1...16
PTC discharge temperature probe (AI type=1...16) <= AL50 set - AL51
differential
Automatic - Manual. If more than AL52 interventions per hour occur. Enter the
functions menu to reset the alarm
flashing
it follows its regulation
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows/they follow its/their regulation
It follows its regulation
Off
It follows its regulation
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
Off with compressor in OFF
iProCHILL
183/205