10.16 SOLAR PANELS WATER PUMP FLOW SWITCH ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Solar panels water pump
Solar coil on/off valve
Other loads
10.17 COMPRESSOR OVERLOAD ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Compressor affected
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
APFL (solar panels pump flow switch alarm)
Solar panel flow AL
(the flow switch alarm is only active with FS01 ≠ 0)
Check DI configured as Solar panels flow switch (DI type=112).
If polarity check not required (AL20=1), after solar panel pump active for AL16
time, if DI active for AL18 time, alarm occur.
If polarity check required (AL20≠1), after domestic hot water pump active for
AL16 time, if DI still keeps the same status as that when solar panel pump is
not working for AL18 time, alarm occur.
DI not active for the time AL19
Automatic – it becomes manual if this alarm active for time AL17 (reset
procedure in functions menu)
flashing
Alarm (DO type=165) + buzzer relays only activated if the flow switch alarm is
activated in normal working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Off when the alarm becomes with manual reset
Active
They follow their regulation
C1tr (compressor n° 1 overload alarm) -...C16tr (compressor n° 16 overload
alarm)
C1 overl ...C16 overl
The alarm is detected after AL27 delay from compressor switch-on. If AL30=1,
the detection also enabled when compressor is off.
With DI configured as Compressor 1...16 thermal overload (DI type=34...49)
active, alarm occur.
If DI not active
Always manual. If more than AL28 compressor interventions occur per hour,
password is request to do reset operation. The password is set in par AL31.
flashing
Alarm relay (DO type=168...183) + buzzer activated
Relay + buzzer activated
it follows its regulation
it follows its regulation
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows/they follow its/their regulation
It follows its regulation
Always off
iProCHILL
182/205