Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
0÷10V proportional output
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Compressors
Pump down solenoid valve
10.5 OIL FLOAT/PRESSURE SWITCH ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
With circuit low pressure pressure switch active. From DI Low pressure
switch circuit 1...4 (DI type=14...17)
If AL08=1, also with unit in stand-by or OFF remote, if circuit low pressure
pressure switch input active
In defrost if AL06=1 if compressor low pressure pressure switch input
active
The alarm is not signalled:
1. in defrost for time AL07 in correspondence with activation of the reverse
valve cycle
2. On compressor switch-on for the time AL01
3. AL02 = 0 the low pressure alarm is inhibited during compressor stopping in
pump down mode and with compressor at a standstill
4. AL02 ≠ 0 the low pressure alarm is inhibited during compressor stopping in
pump down mode and with compressor at a standstill for the time set
Input deactivation
Automatic – it becomes manual after AL05 interventions/hour (reset procedure
in functions menu)
flashing
Alarm relay(DO type=158...161) + buzzer activated
Relay + buzzer activated
it follows its regulation
it follows its regulation
it follows its regulation
It follows/they follow its/their regulation
It follows/they follow its/their regulation
It follows its regulation
It follows its regulation
Off
It follows its regulation
It follows its regulation
Off
off
OPC1-...OPC16 (compressor n°1...16 oil pressure switch alarm)
AL oil C1-...AL oil C16
DI configured as Oil pressure/level switch compressor 1 (DI type=69...84)
activated.
The alarm is not signalled: on compressor switch-on for the time AL12. After
time AL12 it is not signalled with unit in normal working conditions for time
AL13. If AL15 = 0 the alarm is not detected with the compressor off
Input deactivation
Automatic – it becomes manual after AL14 interventions/hour (reset procedure
in functions menu)
flashing
Alarm relay + buzzer activated
Relay + buzzer activated
it follows its regulation
it follows its regulation
iProCHILL
170/205