Emerson Dixell iProChill IPC115D Application Manual page 199

Table of Contents

Advertisement

1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
ACF11
Heat recovery enabled but
 Not all resources needed are defined in a circuit (condensing probe, heat
recovery request d.i. heat recovery relay).
If rC01=3, condensing probe not configured (AI type=48...55).
If rC01≠3, DI heat recovery request not configured (DI type=60...63).
Free cooling or domestic hot water is enabled (FC01≠0 or FS01≠0).
ACF12
At least one inverter exist in the unit:
 Unit configured as Moto-condensing unit (CF04=1) or not using
proportional temperature regulation (ST11≠0).
 For the compressor with inverter, no relevant resource configured. Such
as compressor modulating output (AO type=11...14 or 28...31),
compressor direct start-up relay (e.g. for comp1, DO type=76).
For relay Management VI valve 14 (DO type=193) and Management VI valve
16 (DO type=195), one relay is configured while another one is not configured.
ACF13
One of 16 compressors weight is different to 0. Parameters CO19...CO34 are
not all set to 0.
ACF14
The temperature control has been configured on two circuits (ST12 = 1) but:
 the second circuit is not configured or circuits 3 or 4 are configured
 free cooling or recovery or domestic hot water are enabled (FC01≠0 or
rC01≠0 or FS01≠0)
ACF15
Free cooling enabled but:
If FC01=1/2/3:
 the on/off valve (DO type=38) and the damper proportional output (AO
type=5 and 22) are not defined
 the evaporator water inlet (AI type=17) not configured
 if CF01≠0, system water inlet temperature probe not configured (AI
type=33)
 2 external air temperature probes are all not configured (AI type=34 and
35)
If FC01=4, any resource below is not configured:
 system water inlet temperature probe (AI type=33)
 external air temperature probe (AI type=34)
 external air temperature probe (AI type=35)
 on/off valve (DO type=38) and ON/OFF fan (DO type=39)
 free-cooling mixer valve (AO type=5 or 22)
ACF16
Production of domestic hot water enabled (FS01≠0) but:
 the unit is configured as air/air (CF01 = 0)
 the domestic hot water pump outlet relay (DO type=75) or domestic hot
water valve 1(DO type=68) are not defined
 the domestic hot water regulation probe 1(AI type=44) is not defined
 FS01=2 and PA01=2 and FS49=0
iProCHILL
199/205