14 Alarm Signals
Message
Cause
P1
Room probe failure
P2
Evaporator probe
failure
P3
Third probe failure
P4
Fourth probe failure
HA
Maximum tempera-
ture alarm
LA
Minimum tempera-
ture alarm
HA2
Condenser high tem-
perature
LA2
Condenser low tem-
perature
dA
Door open
EA
External alarm
CA
Serious external
alarm (i1F=bAL)
CA
Pressure switch alarm
(i1F=PAL)
rtc
Real time clock alarm
rtF
Real time clock board
failure
Table 14-1 - Alarm Signals
14.1. Silencing Buzzer/Alarm
Relay Output
If tbA = y, the buzzer and the relay are is silenced
by pressing any key.
If tbA = n, only the buzzer is silenced while the
alarm relay is ON until the alarm condition recovers.
Silencing Buzzer/Alarm Relay Output
Outputs
Compressor output acc.
to par. Con and CoF
Defrost end is timed
Outputs unchanged
Outputs unchanged
Outputs unchanged
Outputs unchanged
It depends on the Ac2
parameter
It depends on the bLL
parameter
Compressor and fans re-
start
Output unchanged
All outputs OFF
All outputs OFF
Alarm output ON; Other
outputs unchanged; De-
frosts according to par.
IdF Set real time clock
has to be set
Alarm output ON; Other
outputs unchanged; De-
frosts according to par.
IdF Contact the service
14.2. Alarm Recovery
Probe alarms P1, P2, P3, and P4 start some sec-
onds after the fault in the related probe; they automat-
ically stop some seconds after the probe restarts
normal operation. Check connections before replac-
ing the probe. Temperature alarms HA, LA, HA2,
and LA2 automatically stop as soon as the tempera-
ture returns to normal values.
Alarms EA and CA (with i1F = bAL) recover as
soon as the digital input is disabled.
Alarm CA (with i1F = PAL) recovers only by
switching OFF and ON the device.
14.3. Other Messages
Message
Pon
Keyboard unlocked
PoF
Keyboard locked
noP
In programming mode:
No parameter is present
In Pr1 on the display or in dP2, dP3, dP4:
The selected probe is not enabled
Table 14-2 - Additional Display Messages
Output
Alarm Signals • 19