1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
ACF8
One or more compressors have been configured using parameters CF05 and
CF08 but the relevant main relays are not configured:
For compressor 1 to 8:
Intermittent valve relay (DO type=52...59) not configured when
enabled by ON/OFF times (CO10 and CO11) ≠ 0 or vice versa (relay
configured but function is not enabled).
No unloader (e.g. for comp. 1, DO type=79) and no gas by-pass
(e.g. for comp.1, DO type=83) configured when by-pass time (CO15)
is ≠ 0 or vice versa (relay configured but function is not enabled).
If CO12=0, compressor in direct start mode, but configured part-
winding/star-delta start-up relays (e.g. for comp.1, DO type=77, 78).
If CO12=1, compressor in part winding start mode, but relay for part
winding start-up is not configured. (e.g. for comp.1, DO type=77). Or
configured redundant relay as star-delta (e.g. for comp.1, DO
type=78).
If CO12=2, compressor in Star-delta start mode, but relevant relays
are not configured (e.g. for comp.1, DO type=77, 78).
No full match between relays configuration and unloaders defined on
parameters CF09 – CF12.
For compressor 9 to 16:
No direct start-up relays configured (e.g. for comp.9, DO type=140).
For auxiliary heating, if it is disabled (AH01=0), but relevant resource are
configured or vice versa (resource not configured but function is enabled).
Such as DI for heater (DI type=114/115), relay Auxiliary heating 1...4 step (DO
type=188...191), AO modulating auxiliary heating (AO type=15/32).
ACF9
evaporator pumps
defined (PA01 ≠ 0) but no relay (DO type=2 and 3) is configured
not defined (PA01 = 0) but a relay is configured
condenser pump
defined (PA17 ≠ 0) but no relay (DO type=8 and 9) is configured
not defined (PA17 = ≠ 0) but a relay is configured
Pump rotation
PA05>=3, rotation at working hours, but hours set point PA07=0.
PA21>=3, rotation at working hours, but hours set point PA23=0.
Evaporator pump for anti-freeze configuration alarm
if PA09 = 2 and PA10 = 0
if PA09 = 2 and PA10 ≠ 0, but no probes selected by PA10 are
configured for managing the function
Condenser pump for anti-freeze configuration alarm
if PA25 = 2 and PA26 = 0
if PA25 = 2 and PA26 ≠ 0, but no probes selected by PA26 are
configured for managing
ACF10
If CF04=0 (not condensation unit), no temperature control probe (in chiller
mode ST09, in heat pump mode ST10) is configured correctly (it does not exist
or is not NTC).