10.42 UNIT CONFIGURATION
Alarm code
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
ACF1
If defrost is enabled (dF01≠0)
dF26=0 (0=Defrosting cycle start in unit independently) and dF27≠0
(0=Defrosting cycle end in unit independently).
dF26=2 (2 = if at least one has reached the request for defrosting to start)
and dF27≠1 (1=if both have reached the defrost end status).
If more than one circuit is configured, FA06=0 and dF33=0 and
dF26/dF27=0.
Set par AH16=1(1=Enable the auxiliary heater in defrost) and dF32=1 (1=
Supply fan doesn't work during defrost).
ACF2
Unit configured as ON/OFF or proportional control of the condensation fan
(FA01=2/3/4), but the relevant probes and circuits are not configured.
(It should has: FA06=1(separate condensation), 1 probe per circuit. FA06=0
(unique condensation), at least 1 probe. FA06=2 (Circuit couple unique
condensation), at least 1 probe and 1 circuit per couple.)
In case of fan with step regulation (FA01=2/3), any one of the following
rules is not respected:
FA10 < FA11 < FA25 < FA26.
FA19 < FA20 < FA29 < FA30.
FA35 < FA36 < FA41 < FA42.
In addition, make sure the step band <= step n set point – setp n-1 set point. For
example: FA12 <= FA11-FA10.
In the case of proportional regulation (FA01=4) with chiller enabled (CF02
=1/3), at least one of the following rules is not respected:
FA10 + FA12 + FA13 < FA11
FA13 < FA14
In the case of proportional regulation (FA01=4) with heating enabled
(CF02=2/3) at least one of the following rules is not respected:
FA19 + FA22 + FA21 < FA20
FA22 < FA23
In the case of proportional regulation (FA01=4) with heating enabled
(CF02=2/3) and dF33=2 at least one of the following rules is not respected:
FA35 + FA38 + FA37 < FA36
FA38 < FA39
If heat pump is enabled (CF02=2/3) and defrost enabled (dF>0), but the
relevant condensating/evaporating probes are not configured.
If PWM regulation is enabled (OUT5 and/or OUT6 configured as PWM
output) continuous power supply has been selected (SP13 = 2)
ACF3
Two digital/analogue inputs configured with the same function.
If a compressor is configured, but relative compressor relays (Compressor
1...16 Direct start-up relay) are not configured.
If a compressor is not configured, but configured relative resources. Such
as Discharge PTC probe and DI Compressor discharge thermostat and DI
Compressor thermal overload and DI Oil pressure/level switch compressor.
If a circuit is not configured, but configured relative resources. For example,
for circuit1, configured probes which AI types are 36, 48, 52 and 56.
Configured DI which DI types are 6, 10, 14 and 85.
If FA06=0 (Unique condensation), configure redundant DI for fan overload
(DI type=51-55).
If FA06=1 (Separate condensation), configure redundant DI for fan overload
(DI type=54/55).
If FA06=2 (Circuit couple unique condensation), configure redundant DI for fan
overload (DI type=50-53).