CO 71
Minimum activation time for VI valves
Parameter
Description
SL 1
Compressors stepless adjustment
0 = not active function
1 = Bitzer compressor active function
2 = Fu Sheng compressor active function
SL 2
Pulses number to consider the stepless compressors of circuit 1 to 100%
SL 3
Pulses number to consider the stepless compressors of circuit 2 to 100%
SL 4
Pulses number to consider the stepless compressors of circuit 3 to 100%
SL 5
Pulses number to consider the stepless compressors of circuit 4 to 100%
SL 6
Delay pulse valves
SL 7
Minimum interval between two consecutive pulses
SL 8
Maximum interval between two consecutive pulses
SL 9
Dead band in chiller operation
SL 10
Dead band in heat pump operation
PA 1
Evaporator pump/supply fan operation mode
0 = Absent (pump and supply fan are not controlled).
1 = Continuous operation: the pump/supply fan is activated when the
machine is switched on (chiller/h.p. selection).
2 = Working on demand of the compressors: the water pump/supply fan
are linked with the compressors being switched on and off.
PA 2
Compressor ON delay from pump/ supply fan start
PA 3
Evaporator water pump/supply fan OFF delay from when the compressors
are shut off
PA 4
Deactivation Pump Delay from when the unit is Switched Off
PA 5
Pump Activation and Rotation:
0 = No Rotation;
1 = Manual Rotation;
2 = Start Rotation;
3 = Rotation at Hours;
4 = Rotation at Start and Hours
PA 6
Manual Pump Inversion:
0= Pump 1 On;
1= Pump 2 On;
PA 7
No. of hours for forced evaporator pump rotation
PA 8
Simultaneous pump running time after forced pump rotation
PA9
Determines the evaporator water pump/s anti-freeze operation when the
device is OFF or on Stand-by
0 = always OFF in remote OFF or Stand-by
1 = ON, parallel with the anti-freeze heaters
2 = on in remote OFF or Stand-by, depending on the temperature control
request
PA10
Temperature control probe for anti-freeze evaporator water pump/s operation
0 = disabled
1 = evaporator input
2 = evaporator output 1/2
3 = evaporator output 3/4
4 = evaporator output 1/2/3/4
5 = evaporator output 1/2/3/4 and common output
6 = external air temperature
PA11
Evaporator water pump activation set point in anti-freeze mode on the
temperature control probe
PA12
Evaporator water pump differential deactivation in anti-freeze mode on the
temperature control probe
PA 13
Main pump/supply fan timer setting
PA 14
Evaporator no. 2 pump timer setting
PA 15
Hot start set-point
PA 16
Hot start differential
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
Stepless compressor
Water pump
Evaporator water pump control
Evaporator water pump operation with anti-freeze alarm
Evaporator water pump maintenance request
Hot start function of the supply fan air/air unit
Condenser water pump management
0
250
sec
min
max
um
Resolution
0
2
1
250
1
250
1
250
1
250
1
250
1
SL8
Sec
SL7
250
Sec
0.1
25.0
°C
1
45
°F
0.1
25.0
°C
1
45
°F
0
2
0
250
Sec
0
250
Sec
0
250
Sec
0
4
0
1
0
999
Hr
0
250
Sec
0
2
0
6
-50.0
110
°C
-58
230
°F
0.1
25.0
°C
0
45
°F
0
999
Hr
0
999
10 Hr
-50.0
110
°C
-58
230
°F
0.1
25.0
°C
1
45
°F
iProCHILL
0.1 sec
Dec
int
Dec
int
10 Sec
10 Sec
10 Sec
10Hr
Dec
int
Dec
int
10 Hr
10 Hr
Dec
int
Dec
int