10.3 COMPRESSOR HIGH DISCHARGE THERMOSTAT ALARM FROM DIGITAL INPUT
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
Action
Regulators
Alarm
Reverse valve
Recovery valve
Free-cooling on/off valve
Auxiliary relay
0÷10V proportional output
Idle running valve
Supply ventilation
Condensation ventilation
Support/boiler/anti-freeze
Pump/and water evaporator
and condenser
Compressor affected
Compressor not affected
Pump down solenoid valve
10.4 LOW PRESSURE PRESSURE SWITCH ALARM
AL 1
Low pressure alarm delay from a digital/analogue input
AL 2
Defines low pressure alarm operation with pump-down enabled
0 = independent from the pump down
1 = blocks the compressors until the pressure switch is disabled
2 = lets the compressors reach peak values
AL 5
Maximum number of interventions per hour of the low pressure alarm from a
digital/analogue input. If the number exceeds AL05 the alarm becomes
manual reset.
Reset is always manual if AL05 = 0
Reset is always automatic if AL05 = 60
Reset moves from automatic to manual if AL05 moves from 1 to 59
AL 6
Low temperature / pressure alarm in defrost mode
0 = not enabled
1 = enabled
AL 7
Low temperature / pressure alarm delay in defrost mode
Delay time between alarm condition occurrence and reaction by device
AL 8
Low temperature/pressure alarm with the unit in remote OFF or Stand-by
mode
0 = alarm detection disabled
1 = alarm detection enabled
Alarm code
Display in keyboard
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
C1dt...C16dt (compressor 1...16 high discharge thermostat alarm)
Hi temp C1-...Hi temp C16
With unit in ON and compressor discharge thermostat digital input active.
From DI: Compressor 1...16 discharge thermostat (DI type=18...33)
Input deactivation
Reset is always manual if AL11 = 0
Reset is always automatic if AL11 =60
Reset passes from automatic to manual if AL11 goes from 1 to 59
(reset procedure in functions menu)
flashing
Alarm relay + buzzer activated
Relay + buzzer activated
it follows its regulation
it follows its regulation
it follows its regulation
It follows/they follow its/their regulation
It follows/they follow its/their regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Off
It follows its regulation
It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
b1LP-...b4LP (circuit n° 1...4 low pressure pressure switch alarm)
Low press circ1-... Low press circ4
0
250
Sec
0
2
0
60
0
1
0
250
Sec
0
1
iProCHILL
169/205