10.43 FUNCTION NOT AVAILABLE ALARM
Alarm code
Display in keyboard
Cause of activation
Reset
Reset
Icon
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
ACF17
one or more pressure probes defined on a XEV20D module which is not
configured by parameters Et09 – Et16
when SP01 <=1 and Et02≠3 or when SP01>=2 and Et02≠4, configured
XEV20D probes as pressure type.
ACF18
If stepless compressor is enabled (SL01≠0):
SL06>=SL07*10
ST11 ≠ 2 (2=neutral zone regulation)
In one circuit, more than one compressor is configured (CF05...CF08>
1)
compressor is configured but relevant relay Compressor 1...4
intermittent valve is not configured (DO type=52...55).
ACF19
Probe selected by Un05 is not configured.
Probe selected by Un10 is not configured.
Conf AL1...Conf AL19
Incorrect programming
Correct programming
Automatic
flashing
Alarm relay (DO type=1) + buzzer activated
Relay + buzzer activated
Off
AfnA (Function not available alarm)
Func.not available
Incorrect parameter configuration, enabled some function that not available
yet.
Set ST11 >2
Set DP05-DP08 value >0
Set SP02 =6
Set SP12=1
Set CO19-CO34 value >0
If CO12=2 (Star-delta start-up), relay Star-delta relay is no configured
on board, they are configured in expansion IO board.
If SL01≠0(stepless compressor enabled)
o
CO09=1/3.
No relays configured as Compressor 1...4 Unloader 1(DO
o
type=79,87,95,103)
Relays (Screw) Compressor 1...4 intermittent valve (DO
o
type=52-55) are not configured on board, they are configured in
expansion IO board.
Relays Compressor 1...4 Unloader 2(DO type=80,88,96,104)
o
are not configured on board, they are configured in expansion IO
board.
Correct programming