Emerson Dixell iProChill IPC115D Application Manual page 131

Table of Contents

Advertisement

Pd 8
Maximum number of pump down alarm interventions per hour, at started-up.
Exceeding this limit, the alarm must be reset manually, it will be saved in
the log and the alarm relay + buzzer will be activated
Reset is always manual if Pd8 = 0
Reset is always automatic if Pd8 =60
Reset switches from automatic to manual if Pd8 falls between 1 and 59
and based on the configuration of Par. Pd9
Pd 9
Pump down alarm automatic or manual reset activation upon start-up
0= the alarm remains in automatic reset even if the number of
interventions per hour is met
1=enables manual reset when the number of interventions per hour is
met
Un 1
Comp. unloading set point of the evaporator input high water temperature in
chiller mode
Un 2
Compressor unloading differential from the evaporator input high water
temperature
Un 3
Delay for the compressor unloading function to be inserted by an evaporator
input high water temperature
Un 4
MAX time in compressor unloading function by an evaporator input high water
temperature
Un 5
Analogue input configuration for control of the unloading function of the
evaporator high water temperature
Un 6
Compressor unloading set point from the evaporator low water temperature
Un 7
Compressor unloading differential from the evaporator low water temperature
Un 8
Delay for the compressor unloading function to be inserted by an evaporator
input low water temperature
Un 9
MAX time in compressor unloading status due to the evaporator low water
temperature
Un 10
Analogue input configuration for control of the unloading function of the
evaporator low water temperature
Un 11
Condensing temperature/pressure compressor unloading set point
Un 12
Condensing temperature/pressure compressor unloading differential
Un 13
Evaporation pressure compressor unloading set point
Un 14
Evaporation pressure compressor unloading differential
Un 15
MAX time in temperature / pressure compressor unloading status
Un 16
Choice of steps for circuit to insert in unloading mode
Un 17
Not used
Parameter
Description
FA1
Fan regulation
0= absent
1= always ON
2 =ON/OFF step insertion
3= continuous ON/OFF step insertion
4= speed proportional regulator
FA2
Fan working mode
0= depending on the compressor
1= independent from the compressor
FA3
MAX speed fan peak time after ON (TRIAC) At every start-up the fan is
powered at maximum voltage for time FA03, irrespective of the
condensation temperature/pressure. When this elapses, the fan
continues at the speed set by the regulator.
FA4
Fan phase displacement analog output 5 (only if configured as PWM /
phase cut)
FA5
Fan phase displacement analog output 6 (only if configured as PWM /
phase cut)
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
Unloading Function
Evaporator water high temperate unloading
Evaporator water low temperate unloading
Chiller condensation unloading
Evaporation unloading
Condensing fan
0
60
0
1
-50.0
110.0
°C
-58
230
°F
0.1
25.0
°C
0
45
°F
0
250
Sec
0
250
Min
1
51
-50.0
110.0
°C
-58
230
°F
0.1
25.0
°C
0
45
°F
0
250
Sec
0
250
Min
1
51
-50.0
110.0
°C
-58
230
°F
0.0
50.0
Bar
0
725
Psi
0.1
25.0
°C
0
45
°F
0.1
14.0
Bar
1
203
Psi
-1.0
50.0
Bar
-14
725
Psi
0.1
14.0
Bar
1
203
Psi
0
250
Min
1
8
min
max
um
Resolution
0
4
0
1
0
250
Sec
micro
0
8
sec
micro
0
8
sec
iProCHILL
Dec
int
Dec
int
10 sec
Dec
int
Dec
int
10 sec
Dec
int
Dec
int
Dec
int
Dec
int
Dec
int
Dec
int
250s
250s
131/205