Emerson Dixell iProChill IPC115D Application Manual page 130

Table of Contents

Advertisement

PA 17
Condenser pump operation mode
0 = Absent (pump not controlled).
1 = Continuous operation: the pump being switched on and off is linked with
the unit being switched on and off.
2 = Working on demand of the compressors: pump switch-on and off is
linked with the compressors being switched on and off.
PA 18
Compressor ON delay from condenser pump start-up
PA 19
Condenser pump OFF delay from compressor shut off
PA 20
Deactivation pump delay from when the unit is switched off
PA 21
Pump activation and rotation:
0 = No Rotation;
1 = Manual Rotation;
2 = Start Rotation;
3 = Rotation at Hours;
4 = Rotation at Start and Hours
PA 22
Manual pump inversion:
0 = Pump 1 On;
1 = Pump 2 On
PA 23
No. of hours for forced condenser pump rotation
PA 24
Simultaneous pump running time after forced condenser pump rotation
PA 25
Condenser water pump/s anti-freeze operation when the device is OFF or on
Stand-by
0 = always OFF in remote OFF or Stand-by
1 = ON, parallel with the anti-freeze heaters
2 = on in remote OFF or Stand-by, depending on the temperature control
request
PA 26
Condenser anti-freeze temperature control probe alarm
0 = disabled
1 = common condenser water input probe
2 = common condenser water input probe and condenser input 1/2
3 = common condenser water input probe and condenser input 3/4
4 = condenser water output probe 1/2
5 = condenser water output probe 3/4
6 = condenser output 1/2/3/4
7 = condenser output 1/2/3/4 and common output
8 = external air temperature
PA 27
Condenser water pump activation set point in anti-freeze mode on the
temperature control probe
PA 28
Condenser water pump differential deactivation in anti-freeze mode on the
temperature control probe
PA 29
Condenser pump timer setting
PA 30
Condenser no. 2 pump timer setting
Pd 1
Pump down operation
0= function disabled
1= disabled with pump down
2= disabled and enabled with pump down
3= disabled with pump down only in chiller mode
4= enabled with pump down and disabled with pump down only in chiller
mode
Pd 2
Pump down pressure setting (see pump down chapter)
Pd 3
Pump down pressure differential (see pump down chapter)
Pd 4
Maximum time in Pump down when started-up and stopped (see pump down
chapter)
Pd 5
Pump down time upon start-up
0 = function disabled
Pd 6
Pump down time upon shutdown
0 = function disabled
Pd 7
Maximum number of pump down alarm interventions per hour, at stopped.
When exceeded, the alarm is recorded and displayed on the
screen with a code and the relay alarm + buzzer is activated
Reset is always manual if Pd7 = 0
Reset is always automatic if Pd7 =60
Reset switches from automatic to manual if Pd7 falls between 1 and 59
1592025050 iProChill v2.5 10D00 AG v1.3 GB 18.02.2016.docx
Condenser water pump operation with anti-freeze alarm
Condenser water pump maintenance request
Pump down function
Pump down
Timed pump down
Pump down alarm
0
2
0
250
Sec
0
250
Sec
0
250
Sec
0
4
0
1
0
999
Hr
0
250
Sec
0
2
0
8
-50.0
110
°C
-58
230
°F
0.1
25.0
°C
1
45
°F
0
999
Hr
0
999
Hr
0
4
0.0
50.0
Bar
0
725
psi
0.1
14.0
Bar
1
203
Psi
0
250
Sec
0
250
Sec
0
250
Sec
0
60
iProCHILL
10 Sec
10 Sec
10 Sec
10Hr
Dec
int
Dec
int
10 Hr
10 Hr
Dec
int
Dec
int
130/205