Appendix 1.1 G(P).Offgan - Mitsubishi Electric MELSEC Q Series User Manual

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

APPENDICES

Appendix 1.1 G(P).OFFGAN

Switches the mode of the Q62DA-FG. (Normal mode to offset/gain setting mode,
offset/gain setting mode to normal mode)
Internal device
Setting
(System, user)
data
Bit
Word
(S)
[Instruction
[Execution
symbol]
condition]
G.OFFGAN
GP.OFFGAN
Setting
data
Un
Start I/O number of the module
Mode switching
0: Switching to normal mode
(S)
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to
offset/gain setting mode".
(1) Function
(2)
App - 2
Link direct device
J \
File
register
Bit
Command
Command
Setting data
Description
Switches the mode of the Q62DA-FG.
• Normal mode to offset/gain setting mode (Offset/gain setting mode flag (XA)
turns on)
• Offset/gain setting mode to normal mode (Offset/gain setting mode flag (XA)
turns off)
POINT
(1) When the offset/gain setting mode is switched to the normal mode, Module
ready (X0) turns from off to on.
Note that initial setting processing will be executed if there is a sequence
program that makes initial setting when Module ready (X0) turns on.
(2) D/A conversion is discontinued if the mode is switched (from the normal mode
to the offset/gain setting mode or from the offset/gain setting mode to the
normal mode).
To resume D/A conversion, switch the mode to the normal mode if it is set to
the offset/gain setting mode, and then turn on and off Operating condition
setting request (Y9).
Operation error
No errors.
Usable devices
Intelligent
function
Index
module
register
device
Z
Word
U \G
G.OFFGAN
GP.OFFGAN
Setting range
0 to FE
0 ,1
MELSEC-Q
Constant
Others
K, H
$
Un
(S)
Un
(S)
Data type
Binary 16 bits
H
Binary 16 bits
App - 2