Mitsubishi Electric MELSEC Q Series User Manual page 170

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

APPENDICES
Device
CH2 Industrial shipment settings
(S) + 10
offset value (used for monitor output)
CH2 Industrial shipment settings gain
(S) + 11
value (used for monitor output)
CH1 User range settings offset value
(S) + 12
(used for D/A)
CH1 User range settings gain value
(S) + 13
(used for D/A)
CH2 User range settings offset value
(S) + 14
(used for D/A)
CH2 User range settings gain value
(S) + 15
(used for D/A)
CH1 User range settings offset value
(S) + 16
(used for monitor output)
CH1 User range settings gain value
(S) + 17
(used for monitor output)
CH2 User range settings offset value
(S) + 18
(used for monitor output)
CH2 User range settings gain value
(S) + 19
(used for monitor output)
1 Set only Pass data classification setting (S)+2. If data is written to the area set by the system, the offset/gain values
will not be read properly.
Sequence program
G.OGLOAD instruction
Completion device (D)
Status display device
at completion (D)+1
App - 5
Control data
Item
(1)
Functions
(a)
Reads the offset/gain values of the user range setting of the Q62DA-FG to
the CPU.
(b)
There are two types of interlock signals for the G(P).OGLOAD instruction:
the completion device (D) and the status display device at completion (D) +
1.
1)
Completion device
Turns on in the END processing of the scan where the G(P).OGLOAD
instruction is completed, and turns off in the next END processing.
2)
Status display device at completion
Turns on and off depending on the completion status of the
G(P).OGLOAD instruction.
Normal completion
Abnormal completion: Turns on in the END processing of the scan
END processing
END processing
ON
OFF
OFF
OFF
1
(2/2)
Setting data
: Stays off and does not change.
where the G(P).OGLOAD instruction is
completed, and turns off in the next END
processing.
Execution completion of
the G.OGLOAD instruction
MELSEC-Q
Setting range
Set by
System
System
System
System
System
System
System
System
System
System
END processing END processing
ON
ON Abnormal
completion
Normal completion
1 scan
App - 5

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Q62da-fgGx configurator-daSw2d5c-qdau-e

Table of Contents