Mitsubishi Electric MELSEC Q Series User Manual page 101

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-DA)
5 - 22
(4)
Specify the user range setting
Specify a user range used for the offset/gain setting of each channel on the
combo box.
(5)
Set up adjustment values
Set up an adjustment value of the offset value or gain value. Select "1," "10,"
"100," or "1000" on the combo box, however, you can also set up adjustment
values by entering a number (1 to 3000).
(6)
Fine adjustment of voltage output or current output
By clicking the
output for the prepared adjustment value is finely adjusted.
(7)
Write settings into the Q62DA-FG
Write the content set up by operations (2) to (6) into the Q62DA-FG by clicking
the
Registration button.
(a) Precautions
Avoid the following operations during the writing of the data, which has
been set up by operations (2) to (6), into the module after the click of the
Registration
Doing so causes an error in the E
operate properly.
1)
Powering off the programmable controller CPU
2)
Resetting the programmable controller CPU
(8)
Switch to the normal mode
When the offset/gain setting screen is closed by clicking the
the setting operation has finished, the Q62DA-FG's operation mode transits to
the normal mode.
POINT
If an error code is displayed while performing the setting operation, the details and
measure of the error can be confirmed by clicking the
error code display area. In addition, Error code can be cleared by clicking the
Error clear button.
+ button or
- button, the value of voltage output or current
button.
2
PROM data and the Q62DA-FG may not
Close button after
... button to the right of the
MELSEC-Q
5 - 22