3 SPECIFICATIONS

3.4.8 Offset/gain adjustment value specification (buffer memory address 24: Un\G24)

3.4.9 Offset/gain range specification (buffer memory address 25: Un\G25)

3 - 31
(1)
This area is used to set the amount of adjustment for analog output values in the
offset/gain setting mode.
(2)
Turning Set value change request (YC) from off to on increments or decrements
the analog output value by the adjustment value.
(3)
The valid input range is from –3000 to 3000.
When the input value is 1000, the analog output values can be adjusted by about
0.33 V (user range setting 2) and about 0.18 V (user range setting 3) for voltage
output and about 0.67 mA for current output.
(4)
Refer to Section 4.6 for the details of the offset/gain settings.
(1)
This area is used to change the output range in the offset/gain setting mode.
Turning on Channel change request (YB) changes the output range into the set
one.
If a value outside the setting range is set, an error (Error code: 60 ) occurs.
Output range
User range setting 1
User range setting 2
User range setting 3
(2)
Channel change request (YB) is required to be turned on/off to validate the
offset/gain range setting. (Refer to Section 3.3.2.)
(3)
Refer to Section 4.6 for details of offset/gain setting.
MELSEC-Q
Set value
000F
H
000E
H
000D
H