6
PROGRAMMING
6.2.1 Program example using the utility package
6 - 3
(1)
Operation of utility package
(a)
Initial settings (Refer to Section 5.4)
CH1, CH2 D/A conversion enable/disable setting .... "Enable"
CH1 Rate control enable/disable setting ................... "Enable"
CH1 Increase digital limit value ................................. "100"
CH1 Decrease digital limit value ................................ "30"
CH1 Disconnection detection setting......................... "Enable"
CH2 Warning output setting ....................................... "Enable"
CH2 Warning output upper limit value ....................... "10000"
CH2 Warning output lower limit value ....................... "3000"
(b)
Automatic refresh setting (Refer to Section 5.5)
CH1, CH2 Digital value .............................................. D11, D12
CH1, CH2 Output monitor value ................................ D13, D14
Disconnection detection ............................................. D15
Warning output ........................................................... D16
Error code ................................................................... D17
MELSEC-Q
6 - 3