ONLINE MODULE CHANGE
7 - 30
POINT
If the buffer memory values compared with the reference table are not proper, save
and restoration of the user range cannot be executed.
Before executing module control resumption, follow the flowchart in Section 4.6 and
make offset/gain setting in the device test of GX Developer.
To switch modes, set a value to Mode switching setting (buffer memory address
158, 159: Un\G158, Un\G159), and turn on and off Operating condition setting
request (Y9).
Note that if module control is resumed without offset/gain setting being made,
operation will be performed with the default values.
(2) Dismounting of module
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" screen.
MELSEC-Q
7 - 30