Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-DA)
5 - 26
(3)
User range restoration
(a)
Set the user range to be used in the Setting value field of CH
classification setting, and click the
When the user range setting is completed, the set user range is displayed in
the Current value field of CH
(b)
Set the recorded values in the Setting value fields of CH
shipment settings offset/gain values/user range settings offset/gain values.
(c)
Select all the Setting value fields of CH
offset/gain values/user range settings offset/gain values, and click the
Execute test
When write is completed, the set values are displayed in the Current value
fields of CH
range settings offset/gain values.
(d)
Change the Setting value field of Pass data write request to "Request", and
click the
Execute test
Make sure that the indication in the Current value field of Pass data write
request changes from "Request" to "OFF" on completion of write.
Execute test
Pass data classification setting.
button.
Industrial shipment settings offset/gain values/CH
button.
MELSEC-Q
Pass data
button.
Industrial
Industrial shipment settings
User
5 - 26