ONLINE MODULE CHANGE

7.3 Online Module Change Procedure

7.3.1 When industrial shipment setting is used and initial setting was made with
GX Configurator-DA
7 - 4
There are the following Online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
DA has been made or not, and whether the other system exists or not.
Range setting
Industrial shipment setting
Industrial shipment setting
User range setting
User range setting
User range setting
User range setting
(1) Conversion disable
(a)
Take the following steps to disable the conversion:
1)
Set D/A conversion enable/disable setting (buffer memory address 0:
Un\G0) to All channel conversion disable (3
2)
Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3)
Operating condition setting completed flag (X9) turns off from on.
4)
Check that the conversion is stopped by seeing the actual analog
output value.
5)
Turn Operating condition setting request (Y9) from on to off.
Initial setting
GX Configurator-DA
Sequence program
GX Configurator-DA
GX Configurator-DA
Sequence program
Sequence program
MELSEC-Q
Other system
Reference section
Section 7.3.1
Section 7.3.2
Present
Section 7.3.3
Absent
Section 7.3.4
Present
Section 7.3.5
Absent
Section 7.3.6
).
H
7 - 4