Wiring; Wiring Precautions - Mitsubishi Electric MELSEC Q Series User Manual

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4
SETUP AND PROCEDURES BEFORE OPERATION

4.4 Wiring

4.4.1 Wiring precautions

4 - 5
The wiring precautions and examples of module connection are provided below.
In order to optimize the functions of the Q62DA-FG and ensure system reliability,
external wiring that is protected from noise is required.
Please observe the following precautions for external wiring:
(1)
Use separate cables for the alternating-current control circuit and the external
output signals and external supply power of the Q62DA-FG in order to avoid AC
surges and induction effects.
(2)
Do not mount the cables close to or bundle them with the main circuit line, a
high-voltage cable or a load cable from other than the programmable controller.
This may increase the effects of noise, surges and induction.
(3)
Perform a one-point grounding for shielded lines and the shields of sealed
cables.
(4)
A solderless terminal with insulating sleeve cannot be used for the terminal
block. Covering the cable- connection portion of the solderless terminal with a
marked tube or an insulation tube is recommended.
MELSEC-Q
4 - 5