Mitsubishi Electric MELSEC Q Series User Manual page 135

Channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7 - 12
(d)
Enable conversion for a channel to be used by setting D/A conversion
enable/disable setting (buffer memory address 0: Un\G0). Set a digital
value to CH
and turn on and off Operating condition setting request (Y9). Turn on CH
Output enable/disable flag (Y1, Y2) of a channel to be used, and check
whether proper conversion has been made or not.
(Be careful since analog outputs are provided actually.)
(e)
Since the new module is in a default status, it must be initialized by a
sequence program after control resumption.
Before performing initialization, check whether the contents of the
initialization program are correct or not.
1)
Normal system configuration
The sequence program should perform initialization on the leading
edge of Module ready (X0) of the Q62DA-FG.
When control resumption is executed, Module ready (X0) turns on and
initialization is performed. (If the sequence program performs
initialization only one scan after RUN, initialization is not performed.)
2)
When used on remote I/O network
Insert a user device that will execute initialization at any timing
(initialization request signal) into the sequence program. After control
resumption, turn on the initialization request signal to perform
initialization. (If the sequence program performs initialization only one
scan after a data link start of the remote I/O network, initialization is not
performed.)
(5) Resumption of control
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
display the "Online module change" screen again, click the [Execution]
button to resume control. Module ready (X0) turns on.
(b)
The "Online module change completed." screen appears.
Digital value (buffer memory address 1, 2: Un\G1, Un\G2)
MELSEC-Q
7 - 12

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Q62da-fgGx configurator-daSw2d5c-qdau-e